S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
11-8
A5E00105492-03
Table 11-3
Evaluation of the SF LED (software error)
3RVVLEOH(UURUV
UHVSRQVHRIWKH&38
5HPHGLHV
TOD interrupt is enabled and
triggered. However, a
matching block is not
loaded.
(Software/configuration
error)
Calls OB85. CPU
does not STOP if
OB85 is loaded.
Load OB 10 (OB number is
apparent from the diagnostic
buffer).
Start time of the enabled
TOD interrupt was jumped,
e.g. by advancing the
internal clock.
Calls OB80. CPU
does not STOP if
OB80 is loaded.
Disable the TOD interrupt before
you set the time-of-day with SFC
29.
Delay interrupt triggered by
SFC 32. However, a
matching block is not
loaded.
(Software/configuration
error)
Calls OB85. CPU
does not STOP if
OB85 is loaded.
Load OB20 or OB21 (CPU 317-2
DP only) (OB number is apparent
from diagnostic buffer).
Process interrupt is enabled
and triggered. However, a
matching block is not
loaded.
(Software/configuration
error)
Calls OB85. CPU
does not STOP if
OB85 is loaded.
Load OB40 (OB number is
apparent from the diagnostic
buffer).
Status alarm is generated,
but the appropriate OB55 is
not loaded.
Calls OB85. CPU
does not STOP if
OB85 is loaded.
Load OB55
Update alarm is generated,
but the appropriate OB 56 is
not loaded.
Calls OB85. CPU
does not STOP if
OB85 is loaded.
Load OB56
Vendor-specific alarm is
generated, but the
appropriate OB57 is not
loaded.
Calls OB85. CPU
does not STOP if
OB85 is loaded.
Load OB57
Attempt to access a missing
or faulty module. (Software
or hardware error)
Calls OB85. CPU
does not STOP if
OB85 is loaded or, if
OB80 is loaded, the
cycle time is
exceeded a second
time without being
triggered again.
Generate OB 85, the start
information of the OB contains the
address of the relevant module.
Replace the relevant module or
eliminate the program error.
The cycle time was
exceeded. Probably too
many interrupt OBs called
simultaneously.
Calls OB80. CPU
does not STOP if it is
OB80 is loaded or
called for a second
time.
Extension of the cycle time
(STEP 7 - Hardware configuration),
changing the program structure.
Remedy: if required, retrigger cycle
time monitoring via SFC 43
Содержание CPU 312
Страница 10: ... RQWHQWV S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x x A5E00105492 03 ...
Страница 76: ... RQILJXULQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 5 50 A5E00105492 03 ...
Страница 146: ... RPPLVVLRQLQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 9 34 A5E00105492 03 ...
Страница 232: ... ORVVDU S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 13 16 A5E00105492 03 ...