$SSHQGL[
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
12-23
/RZYROWDJHSURWHFWLRQHOHPHQWVIRU!
For the transition points between lightning protection zones 1 <-> 2 we recommend
the surge protection components listed in the table below. This low-voltage
protection must be used in S7-300 for CE compliance.
Table 12-9
Surge voltage protection components for lightning protection zones 1 <-> 2
&RQVHF
QR
&DEOHVIRU
HTXLSWUDQVLWLRQSRLQW
!ZLWK
2UGHU1R
3-phase TN-C system
3 x
DEHNguard 275 surge
arresters
900 600*
5SD7 030
3-phase TN-S system
4 x
DEHNguard 275 surge
arresters
900 600*
5SD7 030
3 x
DEHNbloc/275 surge arrester,
phase L1/L2/L3 to N
900 600*
5SD7 030
3-phase TT system
1 x
DEHNgap C N-PE surge
arrester, N to PE
900 131*
AC TN-S system
2 x
DEHNguard 275 surge
arresters
900 600*
5SD7 030
AC TN-C system
1 x
DEHNguard 275 surge
arresters
900 600*
5SD7 030
1 x
DEHNguard 275
surge arrester, phase L to N
900 600*
5SD7 030
1
AC TT system
1 x
DEHNgap C, N-PE surge
arrester, N to PE
900 131*
2
24 VDC Power Supply
1 x
Blitzductor VT, type AD 24 V -
918 402*
Bus cable
•
MPI, RS485
•
Blitzductor CT surge
arrester, type MD/HF
919 506* and
919 570*
3
•
RS232 (V.24)
1 x
•
per conductor pair
Surge arrester Blitzductor
CT type ME 15 V
919 506* and
919 522*
4
Inputs of digital modules
DC 24 V
1 x
Low-voltage surge arrester
, type FDK 2 60 V
919 993*
5 Outputs
of
digital
modules 24 V
1 x
Low-voltage surge arrester
919 991*
Inputs/outputs of digital
modules
2 x
Surge arrester
•
120 VAC
•
DEHNguard 150
900 603*
6
•
230 VAC
•
DEHNguard 275
900 600*
7 Inputs
of
analog
modules up to 12 V +/-
1 x
Blitzductor CT surge arrester,
type MD 12 V
919 506* and
919 541*
* You can order these components directly from:
DEHN + SÖHNE
GmbH + Co. KG
Elektrotechnische Fabrik
Hans-Dehn-Str. 1
D-92318 Neumarkt
Содержание CPU 312
Страница 10: ... RQWHQWV S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x x A5E00105492 03 ...
Страница 76: ... RQILJXULQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 5 50 A5E00105492 03 ...
Страница 146: ... RPPLVVLRQLQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 9 34 A5E00105492 03 ...
Страница 232: ... ORVVDU S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 13 16 A5E00105492 03 ...