S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
11-23
6WDWLRQVWDWXV
Table 11-13 Structure of station status 1 (byte 0)
%LW
'HVFULSWLRQ
5HPHG\
0
DP slave cannot be addressed by DP master.
•
Is the correct DP address set on the DP
slave?
•
Is the bus connector in place?
•
Does the DP slave have power?
•
Correct configuration of the RS485
Repeater?
•
Perform a reset on the DP slave.
1
DP slave is not ready for data exchange.
•
Wait for the slave to complete start-up.
2
Configuration data sent by DP master to the DP
slave is inconsistent with slave configuration.
•
Was the software set for the correct
station type or DP slave configuration?
3
Diagnostic interrupt, generated by a RUN to
STOP transition on the CPU or by the SFB 75
Diagnostic interrupt, generated by a STOP to
RUN transition on the CPU or by the SFB 75
•
You can read the diagnostic data.
4
Function not supported; e.g. changing the DP
address at software level
•
Check configuration data.
5
This bit is always “0”.
•
-
6
DP slave type inconsistent with software
configuration.
•
Was the software set for the right station
type? (parameter assignment error)
7
DP slave was configured by a DP master other
than the master currently accessing the slave.
•
The bit is always 1 if, for example, you are
currently accessing the DP slave via PG or
a different DP master.
The configuring master's DP address is
located in the ”Master PROFIBUS address”
diagnostics byte.
6WDWLRQ6WDWXV
Table 11-14 Structure of station status 2 (byte 1)
%LW
'HVFULSWLRQ
0
The DP slave requires new parameters and configuration.
1
A diagnostic message was received. The DP slave cannot resume operation until the error
has been cleared (static diagnostic message).
2
This bit is always ”1” if a DP slave exists with this DP address.
3
The watchdog monitor is enabled on this DP slave.
4
DP slave has received control command "FREEZE".
5
DP slave has received control command "SYNC".
6
This bit is always "0".
7
DP slave is disabled, that is, it has been excluded from cyclic processing.
Содержание CPU 312
Страница 10: ... RQWHQWV S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x x A5E00105492 03 ...
Страница 76: ... RQILJXULQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 5 50 A5E00105492 03 ...
Страница 146: ... RPPLVVLRQLQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 9 34 A5E00105492 03 ...
Страница 232: ... ORVVDU S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 13 16 A5E00105492 03 ...