&RPPLVVLRQLQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
9-22
A5E00105492-03
6. Control the PO via menu item
9DULDEOH!(QDEOHFRQWUROYDOXHV
. "Enable PO“
mode remains active until switched off again via
9DULDEOH!(QDEOH32
.
"Enable PO" is also terminated when the connection to the PG goes down.
7. Return to step 4 if you want to specify new values.
1RWH
For example, a message pops up to indicate CPU mode transition from STOP
to RUN or START-UP.
A message also pops up indicating that the "Enable PO" function is selected
while the CPU is in RUN mode.
&RPPLVVLRQLQJ352),%86'3
&RPPLVVLRQLQJ352),%86'3
5HTXLUHPHQWV
Requirement for commissioning a PROFIBUS DP network is:
•
A PROFIBUS DP network has been created.
•
In
67(3
, you have configured the PROFIBUS DP network and you have
assigned all network nodes a PROFIBUS DP address and memory area (see
the Manual
6,0$7,&67(39[&RQILJXULQJKDUGZDUHDQGFRQQHFWLRQVZLWK
67(39[
).
•
Note that you must also set address switches in some of the DP slaves (see the
description of the relevant DP slave).
•
Software requirements are shown in the table below, depending on the CPU:
Table 9-6
Software requirements
&38
2UGHU1R
6RIWZDUHUHTXLUHG
313C-2DP 6ES/313-6CE00-0AB0
314C-2DP 6ES7314-6CF00-0AB0
67(3
V 5.1 or later + SP 4
&20352),%86
V 5.0 or later
315-2 DP
6ES7315-2AG10-0AB0
67(3
V 5.1 or later + SP 4
317-2 DP
6ES7317-2EJ10-0AB0
67(3
V 5.2 + SP 1 or later
Содержание CPU 312
Страница 10: ... RQWHQWV S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x x A5E00105492 03 ...
Страница 76: ... RQILJXULQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 5 50 A5E00105492 03 ...
Страница 146: ... RPPLVVLRQLQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 9 34 A5E00105492 03 ...
Страница 232: ... ORVVDU S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 13 16 A5E00105492 03 ...