&RPPLVVLRQLQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
9-24
A5E00105492-03
Is the DP CPU a DP slave?
If so, you will find that DP slave in the PROFIBUS-DP catalog as
DOUHDG\
FRQILJXUHGVWDWLRQ
. In the DP master, assign a slave diagnostic address to
this DP slave CPU. You must interconnect the DP master with the DP slave
CPU and specify the address areas for data exchange with the DP slave
CPU.
&RPPLVVLRQLQJ
Commission the DP CPU as a DP master in the PROFIBUS subnet as follows:
1. Download the configuration of the PROFIBUS subnet created with
67(3
(preset configuration) to the DP CPU using the PG.
2. Switch on all of the DP slaves.
3. Switch the DP CPU from STOP to RUN.
6WDUWXSRI'3&38DVD'30DVWHU
During start-up, the DP CPU checks the configured preset configuration of its DP
master system against the actual configuration.
If preset configuration = actual configuration, the CPU switches to RUN mode.
If the preset configuration
≠
to the actual configuration, the configuration of
parameter
VWDUWXSLISUHVHWFRQILJXUDWLRQ
z
DFWXDOFRQILJXUDWLRQ
determines
the start-up behavior of the CPU.
6WDUWXSZLWKSUHVHWFRQILJXUDWLRQ
z
DFWXDOFRQILJXUDWLRQ \HV'HIDXOW
VHWWLQJ
6WDUWXSZLWKSUHVHWFRQILJXUDWLRQ
z
DFWXDOFRQILJXUDWLRQ QR
DP CPU switches to RUN.
(BUSF LED flashes if any of the DP slaves
cannot be addressed)
DP CPU remains in STOP mode, and the
BUS LED flashes after the set
0RQLWRULQJ
WLPHIRUWUDQVIHURISDUDPHWHUVWR
PRGXOHV
.
The flashing BUSF LED indicates that at
least one DP slave cannot be accessed. In
this case, check whether all DP slaves are
switched on or correspond with your
configuration, or read out the diagnostic
buffer with
67(3
.
Содержание CPU 312
Страница 10: ... RQWHQWV S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x x A5E00105492 03 ...
Страница 76: ... RQILJXULQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 5 50 A5E00105492 03 ...
Страница 146: ... RPPLVVLRQLQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 9 34 A5E00105492 03 ...