Cable type
Cable plugs
Make
Type
T/W
1)
,
2)
Conductor
cross-section
[mm
2
]
Design
2)
Thermoplastic-insulated cable 15 / 17.5 / 24 kV according to IEC / EN 60502-2 / VDE 0276-620
1- or 3-core cable,
PE and XLPE-insulated
N2YSY (Cu) and N2XSY (Cu)
or
NA2YSY (Al) and
NA2XSY (Al)
Nexans Euromold
K400TB/G, 430TB/G, 480TB/G
T
35...300
screened
K400LB/G
W
35...300
screened
484TB/G
T
70...630
screened
K440TB/G
T
185...630
screened
nkt cables
CB 24-630
T
25...300
screened
AB 24-630
T
25...300
insulated
CB 36-630 (1250)
T
300...630
screened
Südkabel
SET 24
T
50...240
screened
SEHDT 23.1
T
300
screened
SEHDT 23
T
185...630
screened
Prysmian Kabel und Systeme
(Pirelli Elektrik)
FMCTs-400
T
25...240
screened
3M Deutschland
93-EE 705-6 / -95
T
25...95
screened
93-EE 705-6 / -240
T
95...240
screened
TE Connectivity
for 1-core ca-
bles
RICS 51 ... with IXSU
3)
T
25...300
insulated
RSTI-58xx
T
25...300
screened
RSTI-59xx
T
400...800
screened
for 3-core ca-
bles
RICS 51 ... with IXSU
3)
T
25...300
insulated
RSTI-58xx + RSTI-TRFxx
T
25...300
screened
Paper-insulated mass-impregnated cables ≤ 12 kV according to IEC / EN 60055-2 / VDE 0276-621
3-core cable, paper-insu-
lated N(A)KLEY, N(A)KBA,
N(A)KBY
TE Connectivity
RICS 51... with UHGK / EPKT
T
95...300
insulated
3-core cable, paper-insu-
lated N(A)EKBA, N(A)KLEY
RICS 51 ... with IDST 51
3)
T
50...300
insulated
Paper-insulated mass-impregnated cables 15 / 17.5 / 24 kV according to IEC / EN 60055-2 / VDE 0276-621
1-core or 3-core cable, pa-
per-insulated
N(A)EKBA, N(A)KLEY
TE Connectivity
RICS 51 ... with IDST 51
3)
T
35...240
insulated
1)
T = cable T-plug, W= cable elbow plug
2)
Use of current transformers and current sensors in combination with insulated systems is possible on request
3)
Discontinued by the manufacturer