9 | Operation
150/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
5. Insert the operating lever and turn clockwise as far
as it will go.
✓ The position indicator of the earthing switch
shows the EARTHED position.
0000
6. Remove the operating lever.
✓ The locking device returns to its initial position.
7. Fit the padlock (optional) on the locking device at
✓
The three-position disconnector is in EARTHED
position.
0000
9.6.7 L2: Switching the three-position disconnector from EARTHED to OPEN position
☒ Circuit-breaker in OPEN position
☒ Three-position disconnector in EARTHED position
1. Check service readiness [
2. Remove the padlock (optional) from the locking
device of the three-position disconnector.
0000
3. Push the locking device of the three-position
disconnector downwards, and hold it.
✓ The actuating opening of the earthing switch is
open.
0000
4. Insert the operating lever and turn counter-clockwise
as far as it will go.
✓ The position indicator of the earthing switch
shows the OPEN position.
0000
5. Remove the operating lever.
✓ The locking device returns to its initial position.
6. Fit the padlock (optional) on the locking device at
✓
The three-position disconnector is in OPEN position.
0000
9.7 Operating the panel with circuit-breaker type 1.1
This chapter describes the manual operation of panels with circuit-breaker type 1.1 and three-
position disconnector (panel types L and V).
The operations are exemplarily shown for a circuit-breaker feeder (panel type L).
Содержание 8DJH