9 | Operation
160/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
Indication
WEGA 1.2C
WEGA 2.2C
Description
L1
L2
L3
L1
L2
L3
State of the
relay contacts
1)
Red
Green
A0
—
U ≠ 0
U = 0
Operating voltage not present.
A1
U ≠ 0
U = 0
Operating voltage present.
Integrated repeat test passed.
A2
U ≠ 0
U = 0
Operating voltage not present.
A3
U ≠ 0
U = 0
Failure of the operating voltage at phase L1.
Operating voltage present at phases L2 and L3.
Integrated repeat test passed (L2 and L3).
A4
U ≠ 0
U = 0
Voltage present, current monitoring of coupling section below
limit value.
A5
U ≠ 0
U = 0
If "Display Test" button is pressed:
Display test passed.
A6
U ≠ 0
U = 0
In operation:
Voltage present and integrated repeat test passed.
Voltage signal too high.
A7
—
U ≠ 0
U = 0
Auxiliary voltage missing.
1)
LED does not light up:
; LED lights up:
9.9 Replacing HV HRC fuse-links
NOTICE
Unsuitable HV HRC fuse-links or extension tubes
Using untested or incorrect HV HRC fuse-links can damage the fuse box.
⇨ Use only fuse-links tested by Siemens, which are listed in the fuse protection table.
⇨ Do not use HV HRC fuse-links with different characteristics for nominally equal rated
current.
⇨ Any use of other fuse-links must be checked by Siemens in advance. Contact the
Siemens Service Hotline.
NOTICE
Stressed HV HRC fuse-links
When a HV HRC fuse-link has tripped, the HV HRC fuse-links in the two other phases may
also have been stressed.
⇨ Replace the HV HRC fuse-links in all 3 phases.
INFORMATION
Not approved fuse-links for switchgear with a rated voltage of up to 12 kV:
▪ 7.2 kV fuse-links with reference dimension 192 mm
▪ 24 kV fuse-links with reference dimension 292 mm
Observe the design of the fuse slide supplied (reference dimension e=292 mm, optionally
e=442 mm)