9 | Operation
140/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
3. Push the locking device upwards, and hold it.
✓ The actuating opening of the switch-disconnector is open.
4. Insert the operating lever and turn straight clockwise as far as it
will go.
✓ The position indicator of the switch-disconnector shows the
CLOSED position.
5. Remove the operating lever.
✓ The locking device returns to its initial position.
6. Fit the padlock (optional) on the locking device at the desired
position [
Page 137, "Mechanical interlocking with padlock"].
✓
The feeder is connected to the busbar.
9.4.2 Switching the three-position switch-disconnector from CLOSED to OPEN
position
☒ Three-position switch-disconnector in CLOSED position
1. Check service readiness [
2. Remove the padlock from the locking device (optional).
3. Push the locking device upwards, and hold it.
✓ The actuating opening of the switch-disconnector is open.
4. Insert the operating lever and turn straight counter-clockwise as
far as it will go.
✓ The position indicator of the switch-disconnector shows the
OPEN position.
5. Remove the operating lever. The locking device returns to its
initial position.
6. Fit the padlock (optional) on the locking device at the desired
position [
Page 137, "Mechanical interlocking with padlock"].
✓
The feeder is disconnected from the busbar.