Technical data | 4
45/174
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
Transformer
HV HRC fuse-link
S
r
[kVA]
u
K
[%]
I
r
[A]
I
r
[A]
U
r
[kV]
e [mm]
Order number
Make SIBA
Make Mersen
400
4
15.5
31.5
10…17.5
442
30 231 13.31,5
–
31.5
10…24
442
30 006 13.31,5
45DB240V32PTD
500
4
19.3
31.5
10…17.5
442
30 231 13.31,5
–
31.5
10…24
442
30 006 13.31,5
–
40
10…17.5
442
30 231 13.40
–
40
10…24
442
30 006 13.40
45DB240V40PTD
630
4
24.3
40
10…17.5
442
30 231 13.40
–
40
10…24
442
30 006 13.40
–
50
10…17.5
442
30 232 13.50
–
50
10…24
442
30 014 13.50
45DB240V50PTD
63
10…24
442
30 014 43.63
–
800
5…6
30.9
63
10…24
442
30 014 43.63
–
1000
5…6
38.5
80
10…24
442
30 014 43.80
–
1250
5…6
48.2
100
10…24
442
30 022 43.100
–
System operating voltage U
n
20…24 kV
20
4
0.75
3.15
10…24
442
30 006 13.3,15
–
50
4
1.5
6.3
10…24
442
30 006 13.6,3
–
75
4
2.2
6.3
10…24
442
30 006 13.6,3
–
100
4
2.9
6.3
10…24
442
30 006 13.6,3
–
10
10…24
442
–
45DB240V10PTD
125
4
3.6
10
10…24
442
30 006 13.10
45DB240V10PTD
160
4
4.7
10
10…24
442
30 006 13.10
–
200
4
5.8
16
10…24
442
30 006 13.16
45DB240V16PTD
250
4
7.3
16
10…24
442
30 006 13.16
45DB240V16PTD
315
4
9.2
16
10…24
442
30 006 13.16
–
20
10…24
442
30 006 13.20
–
25
10…24
442
–
45DB240V25PTD
400
4
11.6
20
10…24
442
30 006 13.20
–
25
10…24
442
30 006 13.25
45DB240V25PTD
500
4
14.5
25
10…24
442
30 006 13.25
45DB240V25PTD
31.5
10…24
442
30 006 13.31,5
45DB240V32PTD
630
4
18.2
31.5
10…24
442
30 006 13.31,5
45DB240V32PTD
40
10…24
442
30 006 13.40
45DB240V40PTD
800
5…6
23.1
31.5
10…24
442
30 006 13.31,5
–
40
10…24
442
30 006 13.40
45DB240V40PTD
1000
5…6
29
50
10…24
442
30 014 13.50
45DB240V50PTS
63
10…24
442
30 014 43.63
–
1250
5…6
36
50
10…24
442
–
45DB240V50PTS
80
10…24
442
30 014 43.80
–
1600
5…6
46.5
100
10…24
442
30 022 43.100
–
2000
5…6
57.8
140
10…24
442
30 022 43.140
–
U
n
System operating voltage
I
r
Rated current of transformer/fuse-link
S
r
Rated power of transformer
U
r
Operating voltage / rated voltage of fuse-link
u
k
Relative impedance voltage of transformer
e
Reference dimension of fuse-link