3 | Description
22/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
Cable plugs
Connection combination
Cable compartment cover
1)
Make
Type
Design
2)
Arrange-
ment
3)
Mounting
depth [mm]
Deeper by a
[mm]
Depth of floor
opening b [mm]
nkt cables
CB 24-630 + CC 24-630
screened
K + K
290
–
635
2x CB 24-630 with coupling unit CP
630C
screened
K + K
370
250
105
5)
860
715
AB 24-630 + AC 24-630
insulated
K + K
290
105
5)
715
2x AB 24-630 with coupling unit CP
630A
insulated
K + K
370
250
105
5)
860
715
CB 36-630 (1250) + CC 36-630 (1250)
screened
K + K
300
–
635
TE Connectivity
RSTI-58xx + RSTI-CC-58xx
screened
K + K
285
–
635
RSTI-x9xx + RSTI-CC-x9xx
screened
K + K
315
105
715
3M Deutschland
2x 93-EE705-6/xxx with coupling unit
KU 23.2
screened
K + K
363
105
715
1)
Only for 310 mm and 430 mm wide panels. For 500 mm wide panels, no deep cable compartment cover and floor opening are required
2)
Use of current transformers and current sensors in combination with insulated systems is possible on request
3)
K = cable plug, Ü = surge arrester
4)
For 500 mm wide panels, a 105 mm deep cable compartment cover is required
5)
On request
Tab. 10:
Cable plugs for single cable connection and double cable connection with surge arresters (interface type C)
Cable plugs / surge arresters
Connection combination
Cable compartment cover
1)
deeper by a
2)
[mm]
Make
Type
Design
3)
Arrangement
4)
Mounting
depth [mm]
Nexans
(K)430TB/G + 300SA
(K)480TB/G + 800SA
(K)484TB/G + 800SA
screened
K + Ü
290
–
(K)430TB/G + (K)300PB/G + 300SA
screened
K + K + Ü
395
105
5)
(K)480TB/G + (K)800PB/G + 800SA
(K)484TB/G + (K)804PB/G + 800SA
screened
K + K + Ü
400
250
Südkabel
SET (12 / 24) + MUT (13 / 23)
screened
K + Ü
302
105
SEHDT 23.1 + MUT 23
screened
K + Ü
302
105
5)
2x SET (12 / 24) + MUT (13/23) with cou-
pling unit KU 23.2/23
screened
K + K + Ü
476
250
2x SEHDT 23.1 + MUT 23 with coupling
unit KU 23.2/23
screened
K + K + Ü
476
250
SEHDT (13 / 23) + MUT 33
screened
K + Ü
540
250
nkt cables
CB 24-630 + CSA 24...
screened
K + Ü
290
–
AB 24-630 + ASA 24...
insulated
K + Ü
290
105
CB 36-630 (1250) + CSA...
screened
K + Ü
290
–
TE Connectivity
RICS 5139 + RDA...
insulated
K + Ü
275
–
RSTI-58xx + RSTI-CC-58SAxx
screened
K + Ü
285
–
RSTI-58xx + RSTI-CC-68SAxx
screened
K + Ü
292
–
RSTI-x9xx + RSTI-CC-58SAxx
screened
K + Ü
295
–
RSTI-x9xx + RSTI-CC-68SAxx
screened
K + Ü
302
105
3M Deutschland
2x 93-EE705-6/xxx + MUT 23 with cou-
pling unit KU 23.2
screened
K + K + Ü
476
250
1)
Only for 310 mm and 430 mm wide panels. For 500 mm wide panels, no deep cable compartment cover and floor opening are required
2)
Page 21, "Deep cable compartment cover"].
3)
Use of current transformers and current sensors in combination with insulated systems is possible on request
4)
K = cable plug, Ü = surge arrester
5)
For 500 mm wide panels, a 105 mm deep cable compartment cover is required