30 AMP CIRCUIT- LOCK™ DISCONNECT SWITCH WITH LED INDICATORS 

 FOR HBLDS3P, HBLDS3SSP, AND HBLDS3SSRP 

 

 

GENERAL INFORMATION 

CAUTION:

 Disconnect Power Before Servicing. 

WARNING:

 

For use with three-phase Y configuration only. Do not use with delta configuration. 

HBLDS3P 

LED indicators

 (

See Figure A). Perform wiring instructions per PD1782. Provided.*

    

HBLDS3SSP 

LED indicators

 (

See Figure B). Perform wiring instructions per PD2520. Provided.* 

HBLDS3SSRP 

LED indicators (See Figure C). Perform wiring instructions per PD2665.Provided.* 

                                   

* Complete assembly steps up to cover installation. 

 

CIRCUIT BOARD WIRING  INSTRUCTIONS: 

1. See figures A, B, or C. 

WARNING

Accidental dropping or rough handling of cover during installation can cause damage

To aid installation place cover as shown. (See Figures A, B, or C). 
2. Loosen terminal screws and secure (6) black wires with male tabs marked L1, L2, L3, T1, T2, T3 to corresponding terminations 
on switch. Tighten terminal screws to 18 pound-inches (2.0 N

-

m).  Secure green ground wire from circuit board to thinner (width) 

ground buss. Tighten grounding buss terminal screw to 7.1 pound-inches (.800 N

-

m). 

3. Install cover. The handle must be in the OFF position. Tighten the four (4) cover screws to 18 pound-inches (2.0 N

-

m) for 

HBLDS3P, and 24 pound-inches (2.7 N

-

m) for HBLDS3SSP and HBLDS3SSRP. 

 
 

 

            

 

 
 
 
 
 
 
 

                                             
 
 
 
 
 
 
 
 
 

 

     

       

 

 

 

 

 

 
 
 

For top feed or bottom feed conduit 
application it is recommended to 
screw in bottom screw a few 
threads to hold cover temporarily 
while installing circuit board wires or 
servicing switch. 

 

If a bottom feed conduit application is 
desired you may place cover on top of 
enclosure temporarily while installing circuit 
board wires or servicing switch.  

Figure C 

Figure B 

Screw in bottom screw a 
few threads to hold cover 
temporarily while installing 
circuit board wires or 
servicing switch. 

 

 

Wiring Device-Kellems 
Hubbell Incorporated (Delaware) 
1-800-288-6000 
Shelton, CT  06484                                                                                                                                                                              
www.hubbell-wiring.com 

 

PD2790 (Page 1)                    02/17

 

                                          

 

 

 

 

 

 

CAUTION

:  

When completed with wiring fully 
remove support screw and remove 
cover for re-installation. DO NOT 
ROTATE into position. Rotating into 
position can result in damage to the 
circuit board assembly underneath 
the cover. 

 

Figure A 

 

CAUTION

:  

When completed with 
wiring fully remove 
support screw and 
remove cover for re-
installation. DO NOT 
ROTATE into 
position. Rotating into 
position can result in 
damage to the circuit 
board assembly 
underneath the cover. 

 

For top or bottom 
feed application it is 
recommended to 
screw in bottom 
screw a few threads 
to hold cover 
temporarily while 
installing circuit 
board wires or 
servicing switch. 

If a bottom feed 
conduit application 
is desired you may 
place cover on top 
of enclosure 
temporarily while 
installing circuit 
board wires or 
servicing switch.  

CAUTION

:  

When completed with 
wiring fully remove 
support screw and 
remove cover for re-
installation. DO NOT 
ROTATE into 
position. Rotating into 
position can result in 
damage to the circuit 
board assembly 
underneath the cover. 