TX³ RCCBs  
4P Neutral right side - up to 63A

  

 

Cat. N°(s): 4 030 08, 09, 10,  42, 43, 44 

 

 

 

 
 

 

 

 

  

 

CONTENTS                                    PAGE 

1. Description, use................................... 1 
2. Range ................................................. 1 
3. Overall dimensions .............................. 1 
4. Preparation - Connection ..................... 1 
5. General characteristics ........................ 3 
6. Compliance and approvals .................. 7 
7. Curves ................................................. 8 
8. Auxiliaries and accessories ................. 9 
9. Safety .................................................. 9 

 

 

 

 

 

 

 

1. DESCRIPTION - USE 

Residual  current  circuit  breaker  (RCCB)  with  positive  contact 
indication  for  control,  protection  and  isolation  of  electrical  circuits, 
protecting  people  from  direct  and  indirect  contact  and  protecting 
installations from insulation faults. 

Symbol: 

 
 
 
 
 
 

Technology: 

.  Electromagnetic  residual  current  function  with  current-sensing 
relay 

2. RANGE 

Polarity: 

. 4-pole 

Width: 

. 4 modules (4 x 17.8 mm) 

Nominal rating In: 

. 25 / 40 / 63 A

 

Residual current types: 

. AC (sinusoidal differential alternating currents) 

Sensitivity: 

. 30/300 mA 

Nominal voltage and frequency: 

. 400 V~ / 415 V~, 50 Hz with standard tolerances 

Maximum operating voltage: 

. 440 V ~, 50 Hz 
 

 

3. OVERALL DIMENSIONS 

 

4. PREPARATION - CONNECTION 

Mounting: 

. On symmetrical rail EN 60715 or DIN 35 rail 

Operating positions: 

. Vertical             Horizontal          Upside down         On the side 

 

 

 

 

Power supply: 

. From the top or the bottom 

Connection: 

. Inputs and outputs via screw terminals 
. Cage terminals, with disengageable and captive screws (fitted with 
flaps preventing a cable being placed under the terminal, with the 
terminal partly open or closed) 
. Neutral on right 
 

 

  Technical data sheet: F01543EN/01 

Updated on: 01/09/15 

     Created on: 19/03/14 

 

Содержание TX3 RCCBs 4 030 08

Страница 1: ...c residual current function with current sensing relay 2 RANGE Polarity 4 pole Width 4 modules 4 x 17 8 mm Nominal rating In 25 40 63 A Residual current types AC sinusoidal differential alternating cu...

Страница 2: ...Required tools For the terminals 5 5 mm 6 5 mm blade screwdriver recommended Pozidriv n 2 Philips N 2 screwdriver recommended For the latching 5 5 mm blade screwdriver recommended 6 mm maximum Pozidr...

Страница 3: ...accordance with EN IEC 61008 1 Rated breaking and making capacity In accordance with EN IEC 61008 1 In 25 40 A Im 500 A In 63 A Im 630 A Specific use Appropriate to operate in humid atmosphere and po...

Страница 4: ...C D B C D B C D C In 32 A 63 A 125 A 125 A 80 A 4P 400 V 25 A to 63 A 6 kA 10 kA 16 kA 25 kA 36 kA Upstream circuit breaker DX 50 kA DPX 160 DPX 160 residual current 16 kA 25 kA 36 kA 50 kA Downstream...

Страница 5: ...a fuse Downstream Upstream RCCB TX3 gG or aM type fuse Rating 50 A 63 A 80 A 100 A 25 A to 63 A 100 kA 50 kA 15 kA 10 kA Power dissipated by the device RCCB Power dissipated by the device In Rating S...

Страница 6: ...ree of pollution 2 Dielectric strength 2000 V 50 Hz Impulse withstand voltage Uimp 4 kV Protection from false tripping 0 5 s 100 kHz damped recurring wave 200 A 8 20 s wave AC type 250 A Protection cl...

Страница 7: ...ng voltage 400 V 400 V 400 V 400 V Derating at 30 none none none none DC operation Cannot be used with DC Operation at 400 Hz Cannot be used at 400 Hz Operation at 60 Hz Can be used at 60Hz except rat...

Страница 8: ...ide up to 63A Cat N s 4 030 08 09 10 42 43 44 7 CURVES Tripping current curves Tripping time curve depending on the value of the fault current AC TYPE Technical data sheet F01543EN 01 Updated on 01 09...

Страница 9: ...Y For your safety your electrical installation is equipped with residual current protection and this must be tested periodically In the absence of any national regulations on the time period required...

Отзывы: