TX³ RCCBs  
4P Neutral right side - up to 63A

  

 

Cat. N°(s): 4 030 08, 09, 10,  42, 43, 44 

 

 

4. PREPARATION - CONNECTION 

(continued) 

Terminal arrangement: 

 

. Terminals protected against direct finger contact IP20, wired device 

. Alignment and spacing of the terminals permitting shutters with the other products via toothed supply busbars 
. Terminal depth: 14 mm

 

. Terminal capacity: 60 mm²

 

. Screw head: mixed head, slotted head and Philips / Pozidriv no. 2 
. Tightening torques: 

- Minimum / Maximum: 1.2 Nm / 3.5 Nm 
- Recommended: 2.5 Nm

 

Conductor types: 

. Copper cables at the top and bottom of the product 

- Cable cross-section: 

 

Without ferrule 

With ferrule 

Rigid cable 

1 x 0.75 to 50 mm² 
or 
2 x 0.75 to 16 mm² 

Flexible cable 

1 x 0.75 to 35 mm² 
or 
2 x 0.75 to 16 mm² 

1 x 0.75 to 25 mm² 

Required tools: 

. For the terminals: 

- 5.5 mm / 6.5 mm blade screwdriver recommended 
- Pozidriv n°2 / Philips N°2 screwdriver recommended 

. For the latching: 

- 5.5 mm blade screwdriver recommended / 6 mm maximum 
- Pozidriv n°2 / Philips N°2 screwdriver recommended 

Manual actuation: 

. Manual action via ergonomic 2 position handle: 

- I-On, device closed O-Off, device open 

Contact status display: 

. By marking of the product:

 

- I-On : closed contacts

 

- O-Off : open contacts  

Residual current trip display: 

. Handle at the bottom position, the residual current is released

 

Lockout: 

. Padlocks possible in the open or closed positions with padlock support (Cat. No. 4 063 03) and Ø5 mm padlock (Cat. No. 4 063 13) 
or Ø6 mm padlock (Cat. No. 227 97) 

Sealing: 

. Possible in the open or closed positions 

Labelling: 

. Circuit identification by way of a label inserted in the label holder situated on the front of the product 

                                                  

                

                

 

 

 

 

Technical data sheet: F01543EN/01 

Updated on: 01/09/15 

Created on: 19/03/14 

 

 

Содержание TX3 RCCBs 4 030 08

Страница 1: ...c residual current function with current sensing relay 2 RANGE Polarity 4 pole Width 4 modules 4 x 17 8 mm Nominal rating In 25 40 63 A Residual current types AC sinusoidal differential alternating cu...

Страница 2: ...Required tools For the terminals 5 5 mm 6 5 mm blade screwdriver recommended Pozidriv n 2 Philips N 2 screwdriver recommended For the latching 5 5 mm blade screwdriver recommended 6 mm maximum Pozidr...

Страница 3: ...accordance with EN IEC 61008 1 Rated breaking and making capacity In accordance with EN IEC 61008 1 In 25 40 A Im 500 A In 63 A Im 630 A Specific use Appropriate to operate in humid atmosphere and po...

Страница 4: ...C D B C D B C D C In 32 A 63 A 125 A 125 A 80 A 4P 400 V 25 A to 63 A 6 kA 10 kA 16 kA 25 kA 36 kA Upstream circuit breaker DX 50 kA DPX 160 DPX 160 residual current 16 kA 25 kA 36 kA 50 kA Downstream...

Страница 5: ...a fuse Downstream Upstream RCCB TX3 gG or aM type fuse Rating 50 A 63 A 80 A 100 A 25 A to 63 A 100 kA 50 kA 15 kA 10 kA Power dissipated by the device RCCB Power dissipated by the device In Rating S...

Страница 6: ...ree of pollution 2 Dielectric strength 2000 V 50 Hz Impulse withstand voltage Uimp 4 kV Protection from false tripping 0 5 s 100 kHz damped recurring wave 200 A 8 20 s wave AC type 250 A Protection cl...

Страница 7: ...ng voltage 400 V 400 V 400 V 400 V Derating at 30 none none none none DC operation Cannot be used with DC Operation at 400 Hz Cannot be used at 400 Hz Operation at 60 Hz Can be used at 60Hz except rat...

Страница 8: ...ide up to 63A Cat N s 4 030 08 09 10 42 43 44 7 CURVES Tripping current curves Tripping time curve depending on the value of the fault current AC TYPE Technical data sheet F01543EN 01 Updated on 01 09...

Страница 9: ...Y For your safety your electrical installation is equipped with residual current protection and this must be tested periodically In the absence of any national regulations on the time period required...