background image

4 / 9 

 

TX³ RCCBs  
4P Neutral right side - up to 63A

  

 

Cat. N°(s): 4 030 08, 09, 10, 42, 43, 44 

 

 

5. GENERAL CHARACTERISTICS 

(continued)

 

Protection against short-circuits: 

. Association with a circuit breaker: 

 

 

Upstream circuit breaker 

Upstream circuit breaker 

 

 

TX³ 4500 A 

TX³ 6000 A 

Downstream RCCB 

TX3 

Curves 

In 



40 A



40 A

4P - 400 V~ 

25 A to 63 A 

6 kA 

10 kA 

 
 

 

 

Upstream circuit breaker 

 

 

DX³ 4500 / 6 kA 

3P / 4P 3 mod 

DX³ 6000 / 10 kA  DX³ 10000 / 16 kA 

DX³ 25 kA 

DX³ 36 kA 

Downstream 

RCCB 

Curves 

B, C & D 

B, C & D 

B, C & D 

In 



32 A



63 A



125 A



125 A



80 A

4P - 400 V~ 

25 A to 63 A 

6 kA 

10 kA 

16 kA 

25 kA 

36 kA 

 
 

 

 

Upstream circuit breaker 

DX³ 50 kA 

DPX³ 160 / DPX³ 160 + residual current 

16 kA 

25 kA 

36 kA 

50 kA 

Downstream 

RCCB TX3 

Curves 

B, C & D 

 

 

 

 

In 



63 A



160 A



160 A



160 A



160 A

4P - 400 V~ 

25 A to 63 A 

50 kA 

16 kA 

25 kA 

25 kA 

25 kA 

 
 

 

. Association with circuit breakers: case of a double fault, in IT system – Resistance to the Icc of a single pole 

Downstream 

RCCB  

 

Circuit breaker 

upstream 

DX

3

 

3P / 4P 

3 mod 

DX

3

 

3P / 4P 

3 mod 

DX

3

 

1P / 2P / 3P / 4P 

 

4500 A / 6 kA 

6000 A / 10 kA 

At 230 V 

4.5 kA 

6 kA 

10 kA 

At 400 V 

3 kA 

3 kA 

3 kA 

 

 

 

Technical data sheet: F01543EN/01 

Updated on: 01/09/15 

Created on: 19/03/14 

 

 

Содержание TX3 RCCBs 4 030 08

Страница 1: ...c residual current function with current sensing relay 2 RANGE Polarity 4 pole Width 4 modules 4 x 17 8 mm Nominal rating In 25 40 63 A Residual current types AC sinusoidal differential alternating cu...

Страница 2: ...Required tools For the terminals 5 5 mm 6 5 mm blade screwdriver recommended Pozidriv n 2 Philips N 2 screwdriver recommended For the latching 5 5 mm blade screwdriver recommended 6 mm maximum Pozidr...

Страница 3: ...accordance with EN IEC 61008 1 Rated breaking and making capacity In accordance with EN IEC 61008 1 In 25 40 A Im 500 A In 63 A Im 630 A Specific use Appropriate to operate in humid atmosphere and po...

Страница 4: ...C D B C D B C D C In 32 A 63 A 125 A 125 A 80 A 4P 400 V 25 A to 63 A 6 kA 10 kA 16 kA 25 kA 36 kA Upstream circuit breaker DX 50 kA DPX 160 DPX 160 residual current 16 kA 25 kA 36 kA 50 kA Downstream...

Страница 5: ...a fuse Downstream Upstream RCCB TX3 gG or aM type fuse Rating 50 A 63 A 80 A 100 A 25 A to 63 A 100 kA 50 kA 15 kA 10 kA Power dissipated by the device RCCB Power dissipated by the device In Rating S...

Страница 6: ...ree of pollution 2 Dielectric strength 2000 V 50 Hz Impulse withstand voltage Uimp 4 kV Protection from false tripping 0 5 s 100 kHz damped recurring wave 200 A 8 20 s wave AC type 250 A Protection cl...

Страница 7: ...ng voltage 400 V 400 V 400 V 400 V Derating at 30 none none none none DC operation Cannot be used with DC Operation at 400 Hz Cannot be used at 400 Hz Operation at 60 Hz Can be used at 60Hz except rat...

Страница 8: ...ide up to 63A Cat N s 4 030 08 09 10 42 43 44 7 CURVES Tripping current curves Tripping time curve depending on the value of the fault current AC TYPE Technical data sheet F01543EN 01 Updated on 01 09...

Страница 9: ...Y For your safety your electrical installation is equipped with residual current protection and this must be tested periodically In the absence of any national regulations on the time period required...

Отзывы: