3 Operation
3.3
Configuring level (parameterization and structuring mode)
3.3.5 Structuring mode PASt (parameter control)
SIPART DR22 6DR2210
C79000-G7476-C154-03
185
Digital display
Factory
setting
Resolution
Dimen-
sion
Parameter meaning
y
x
w
Adjustment/
setting
sion
Adjustment/
display area
vvc
0.100 -- 10.00
5
128 values/
octave
1
Derivative action gain
cP1
cP3
cP5
cP7
cP9
0.1 -- 100
0.1
0.1
0.1
0.1
0.1
128 values/
octave
1
1
1
1
1
Proportional action factor at SG = 10 %
Proportional action factor at SG = 30 %
Proportional action factor at SG = 50 %
Proportional action factor at SG = 70 %
Proportional action factor at SG = 90 %
tn1
tn3
tn5
tn7
tn9
ia
ble
x
1 -- 9984
9,984
9,984
9,984
9,984
9,984
128 values/
octave
s
s
s
s
s
Integral action time at SG = 10 %
Integral action time at SG = 30 %
Integral action time at SG = 50 %
Integral action time at SG = 70 %
Integral action time at SG = 90 %
tv1
tv3
tv5
tv7
tv9
C
ont
ro
lle
d
va
ri
a
oFF, 1 -- 2992
oFF
oFF
oFF
oFF
oFF
128 values/
octave
s
s
s
s
s
Derivative action time at SG = 10 %
Derivative action time at SG = 30 %
Derivative action time at SG = 50 %
Derivative action time at SG = 70 %
Derivative action time at SG = 90 %
AH1
AH3
AH5
AH7
AH9
C
0.0 -- 10.0
0.0
0.0
0.0
0.0
0.0
0.1
%
%
%
%
%
Response threshold at SG = 10 %
Response threshold at SG = 30 %
Response threshold at SG = 50 %
Response threshold at SG = 70 %
Response threshold at SG = 90 %
Y01
Y03
Y05
Y07
Y09
Auto, 0.0 -- 100.0
0.0
0.0
0.0
0.0
0.0
0.1
%
%
%
%
%
Operating point P-Reg. at SG = 10 %
Operating point P-Reg. at SG = 30 %
Operating point P-Reg. at SG = 50 %
Operating point P-Reg. at SG = 70 %
Operating point P-Reg. at SG = 90 %
SG means: controlling variable for the parameter control
Table 3-7
Parameter list PASt
Error messages
-
tv Err:
If tv.1 to tv.9 have not been set all = off or have not been set all
≠
off, the error message tv Err
appears when returning to the structuring preselection mode after PASt with the Exit key.
Pressing the Enter key:
Error correction possibility by jumping to tv.1 in the structuring mode PASt.
Pressing the Exit key:
Error message is acknowledged, return to the structuring preselection level after PASt, tv.1 to
tv.5 are automatically set to oFF.
-
Y0 Err:
If Y0.1 to Y0.9 have not been set all = AUto or have not been set all
≠
AUto, the error message
Y0 Err appears on returning to the structuring preselection level after PASt with the Exit key.
Pressing the Enter key:
Error correction possibility by jumping to the structuring mode PASt after Y0.1.
Pressing the Exit key:
Error message is acknowledged, return to the strucuring preselection level after PASt, Y0.1 to
Y0.2 are automatically set to AUto.
Содержание 6DR2210
Страница 2: ......
Страница 3: ...SIPART DR22 6DR2210 C79000 G7476 C154 03 1 SIPART DR22 6DR2210 Edition 12 2006 Manual ...
Страница 236: ...Manual 6 Ordering data 234 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 242: ...Manual 7 Application examples for configuring the controller 240 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 260: ...Manual 9 Explanation of abbreviations 258 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 268: ...Manual 266 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 269: ......