2 Installation
2.2 Electrical Connection
2.2.3 Alternative connection for
I
- and U-input
162
SIPART DR22 6DR2210
C79000-G7476-C154-03
+U
H
--
+
U
--
AE+
AE--
M
+
Figure 2-34
Single-pin connection of a non-floating voltage supply with negative polarity to ground
--
U
H
--
+
U
only permitted when
connected for 1 V
+
AE+
AE--
M
Figure 2-35
Single-pin connection of a non-floating voltage supply with positive polarity to ground
Figure 2-34 and Figure 2-35:
The voltage dip on the ground rail between the voltage source and the input amplifier appears
as a measuring error. Only use when ground cables are short or choose a circuit configuration
as shown in figure 2-36!
+U
H
U
--
+
AE+
AE--
M
--
+
Figure 2-36
Double-pin wiring of a voltage source with negative polarity to ground