1.5.10 Restart conditions (S99, S100)
With S99 the restart conditions after mains recovery and manual reset are determined. In
position 0 the controller starts after mains recovery and after a watchdog reset with the
operating mode and with the y which was active before the power failure. This variation must be
used when temporary mains failures are to be expected in slow control circuits.
In position 1 start takes place after mains recovery in manual and Internal operation (in
cascades also with Int
I
) with ys in the K-controller and with the last y in the S-controller. If only
external operating mode or only automatic operation was selected by the structuring, the restart
takes place in these operating modes.
With S100 the optical signaling of mains voltage recovery and reset is determined by flashing of
the digital x-display. The flashing is acknowledged by pressing the Shift key (12) or by an alarm
request via SES.
1.5.11 Serial interface and PROFIBUS-DP (S101 to S107)
With S101 the depth of the SES interventions is preset. Generally all available set data can be
read. In position 0 no transmission and reception of data to the controller is possible. In position
1 only parameters and structures can be transmitted. In the other positions the process
variables wES (external setpoint via the SES) and yES (external manipulated variable via the
SES) and all control signals can be transmitted by the SES. In this position the other possible
sources for the external setpoint or the external manipulated variable are switched off.
The structure switches S102 to S107 determine the transmission procedure through the serial
interface. For further details, see the description ”Serial SIPART DR22 V.28 bus interface”, or-
der number C79000-B7476-C155.
Settings for PROFIBUS-DP: see table 3-8 ”Structure switch tables”, page 187.
Содержание 6DR2210
Страница 2: ......
Страница 3: ...SIPART DR22 6DR2210 C79000 G7476 C154 03 1 SIPART DR22 6DR2210 Edition 12 2006 Manual ...
Страница 236: ...Manual 6 Ordering data 234 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 242: ...Manual 7 Application examples for configuring the controller 240 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 260: ...Manual 9 Explanation of abbreviations 258 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 268: ...Manual 266 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 269: ......