Manual
3 Operation
3.3 Configuring level (parameterization and structuring mode)
3.3.3 Parameterization mode AdAP (Adaptation)
178
SIPART DR22 6DR2210
C79000-G7476-C154-03
Monitoring time
Direction
of the step
Amplitude
trigger
Start of adaptation
Enter key (9)
Adaptation
after process
operation
Repeat
adaptation
Selection level
AdAP
Enter
key
(9)
Pre-adaptation
↗
Presettings
Adaptation LED (4) OFF
Exit
key
(2)
Old parameters
**.o are
overwritten by
new parameters
**.n
2)
see
fig.
3-3,
page
170
if nec. controller
selection
controller
I
or controller
II
,
Switch controller
to manual mode,
set the desired
operating point
and wait for
stationary
condition!
Filters tF
I
, tF
II
and tF1 to tFb
and floating time
tY must be set!
In the S-controller
tA, tE and tY
must be set!
Enter
key (9)
1)
2)
Keys (139
±∆
y
Process operation
level,
see chapt. 3.1,
pg. 167
Switch controller
to automatic
operation, new
parameters **.n
are active
Old
parameters
**.o are
retained
cP.o
AH.o
cP.n
Pid.*
AH.n
Pi or Pid
Switch controller
to automatic
operation, old
parameters **.o
are active
During adaptation
Adaptation LED (4) flashing
Complete process display
cP.n
Pi.*
Exit
key
(2)
Parameterization mode AdAP
by
error mes-
sages
manual
of the adap-
via
tation
Exit key
procedure
see table 3-2, pg. 177
Error
message
display
tU oFF,0.1 to 24 h
dPv nEG, PoS
dY 0.5 to 90 %
**.o Pi or Pid
**.n Strt AdAP
Exit
key
(2)
Exit
key
(2)
Exit
key
(2)
Exit
key
(2)
Exit
key
(2)
aborted adaptation
Adaptation LED (4) OFF
Post adaptation
Adaptation LED (4) ON
old
parameters
new
parameters
Figure 3-5
Parameterization mode AdAP
*
loop order 1 to 8
**
parameter name
1)
Enter function only active in manual operation (in the case of adaptation of the master controller in cascades (S1 = 5/6) master controller
set to Internal and Automatic)
2)
Error message
no AUto
If new parameters are selected and there is parameter control, the flashing error message no AUto appears after pressing the Exit
key (no automatic transfer).
Press the Enter key: Error is acknowledged; return to parameterization mode AdAP; the parameters won by adaptation
can be noted.
Pressing the Exit key: Jump to the parameterization preselection mode AdAP; the new parameters **.n are deleted.
On jumping to the parameterization mode AdAP, Strt AdAP appears in **.n.
Содержание 6DR2210
Страница 2: ......
Страница 3: ...SIPART DR22 6DR2210 C79000 G7476 C154 03 1 SIPART DR22 6DR2210 Edition 12 2006 Manual ...
Страница 236: ...Manual 6 Ordering data 234 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 242: ...Manual 7 Application examples for configuring the controller 240 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 260: ...Manual 9 Explanation of abbreviations 258 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 268: ...Manual 266 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 269: ......