3 Operation
3.3 Configuring level (parameterization and structuring mode)
3.3.12Set structuring mode CAE4/CAE5 -- UNI module(s)
212
SIPART DR22 6DR2210
C79000-G7476-C154-03
The corresponding settings of the CAE4(5) menus for the different signal transmitters are
described below.
The range and thus the current measured value can be corrected with the parameters CA/CE to
compensate tolerances of the transmitters or adjustments with other display instruments.
3.3.12.1 Measuring range for mV (SEnS=Mv.)
D
MA/ME measuring range
Call parameters MA, ME, set range start and full scale:
--175 mV
≤
MA
≤
ME +175
_
C
D
CA/CE fine adjustment
Call parameter CA:
Set signal at the low end of the range, correct the display with CA if necessary.
Call parameter CE:
Set signal at the top end of the range, correct the display with CE if necessary.
3.3.12.2 Measuring range for U, I (SEnS=Mv.)
D
MA/ME measuring range
The setting is made in mV (--175 mV to +175 mV);
The input signal types U and I are set to range 0/20 to 100 mV in the measuring range plug
(6DR2805--8J);
Example:
0 to 10 V or 0 to 20 mA:
2 to 10 V or 4 to 20 mA:
MA = 0,
MA = 20,
ME = 100;
ME = 100
Call parameters MA, ME, set range start and full scale.
D
CA/CE fine adjustment
Call parameter CA:
Set signal at the low end of the range, correct the display with CA if necessary.
Call parameter CE:
Set signal at the top end of the range, correct the display with CE if necessary.
Содержание 6DR2210
Страница 2: ......
Страница 3: ...SIPART DR22 6DR2210 C79000 G7476 C154 03 1 SIPART DR22 6DR2210 Edition 12 2006 Manual ...
Страница 236: ...Manual 6 Ordering data 234 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 242: ...Manual 7 Application examples for configuring the controller 240 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 260: ...Manual 9 Explanation of abbreviations 258 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 268: ...Manual 266 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 269: ......