1 Technical Description
1.5 Functional description of the structure switches
1.5.2
Analog input signal processing freely connected (S4 = 1)
SIPART DR22 6DR2210
C79000-G7476-C154-03
27
The individual function blocks are described below.
1.5.2.1 Arithmetic Ar1 to Ar6
E1
E2
E3
E4
E5
Ar
.6
Ar .F
nr
Ar .1
Ar .2
Ar .3
ncon
ncon
0.000
0.000
1.000
Ar .4
Ar .5
A
E1 · E2 + E3 - E4
E5
A =
E5 is limited to values
≥
0.5 %.
E5
E1 · E2+E3-E4
Ar1 to Ar6
Figure 1-7
Function block Arithmetic Ar1 to Ar6
-- With this function block the four basic arithmetic functions are implemented with appropriate
assignment of inputs 0 and 1 respectively. The preset E3=E4=0, E5=1 gives A = E1
×
E2.
-- Typical process-technical applications are dosing or evaluation (E1
×
E2), range fade-outs
(E1
×
E2+E3) or differentiations (E3 - E4).
1.5.2.2 Function transmitter Fu1 and Fu2
Fu .2
Fu .F
nr
Fu .1
ncon
E
A
A
A = f(E)
-10, 0, 10 bis 90, 100, 110oFPA
E
Fu1, Fu2
Figure 1-8
Function block function transmitter
The function transmitter assigns every value of the input variable E in the range from -10 % to
+110 % an output variable A in the range from -199,9 % to +199,9 % with the function entered
by the user: A = f(E). The function is entered by the parameters ”vertex value 1 to 13” for -10 %
to +110 % of E in intervals of 10 %. Parabolae are set by the computing program between
these vertex values which interlink tangentially the vertex values so that a constant function is
produced. The vertex values at -10 % and +110 % of E are required for the overflow. The last
rise remains constant in the case of further overmodulation of E. When used as a linearizer for
the displays, the linearization function is entered by the 13 vertex values so that the series
circuiting of the sensor function gives a linear equation with the linearization function
(see chapter 1.5.4, figure 1-20 to figure 1-23, page 46).
1.5.2.3 Maximum value selection MA1 to MA3
E1
E2
E3
MA .4
MA .F
nr
MA .1
MA .2
MA .3
ncon
ncon
0.050
Max
A
A = max (E1,E2, E3)
The greatest of the three input values is
connected through to the output.
MA1.F to MA3.F
Figure 1-9
Function block maximum value selection
With the preset the greater value of E1 or E2 is connected through to A and at the same time
limited to the value of E3 (-5 %). Typical applications are maximum value selection circuits and
minimum value limitings.
Содержание 6DR2210
Страница 2: ......
Страница 3: ...SIPART DR22 6DR2210 C79000 G7476 C154 03 1 SIPART DR22 6DR2210 Edition 12 2006 Manual ...
Страница 236: ...Manual 6 Ordering data 234 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 242: ...Manual 7 Application examples for configuring the controller 240 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 260: ...Manual 9 Explanation of abbreviations 258 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 268: ...Manual 266 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 269: ......