SIPART-DR22 Standard controller
PE
N
L
UC 24 C
AC 115 V
AC 230 V
+
--
U
H
--
I
+
ESR
y
R
S1
S2
M
S1
S2
U
H
Attention:
-- All settings starting from the factory setting (APSt) of the
controller
-- The above settings/adaptations are absolutely essential.
Other parameters as required.
Manual
7 Application examples for configuring the controller
236
SIPART DR22 6DR2210
C79000-G7476-C154-03
Example 2
Fixed setpoint controller with S-output, internal feedback.
controlled variable via four-wire transmitter
position feedback y
R
via two-wire transmitter
Block diagram control circuit
The controlled variable x from a four--wire transmitter goes to
the analog input AE1, signal range 4 to 20 mA.
The manipulated variable is switched from the digital outputs via
external coupling relays to the actuating drive.
4 to 20 mA are available ar AE2 as a position feedback (only for
display on the controller)(position feedback potentiometer with
two-wire connection).
The actuating drive has a runtime of 60 s (for 0 to 100 %
deviation).
Alarms:
A1:
xd
±
5 %,
Max. Output to BA1
A2:
x
70 %,
Max. Output to BA2
Note:
The outputs of the S--controller are permanently
assigned to the digital outputs BA7 (+
Δ
y)/BA8 (--
Δ
y)
x
wi
M
y
R
Structure switch Strs
Switch
Value
Meaning
S
2
1
S-controller internal
S
5
2
AE1: 4 to 20 mA
S
6
2
AE1: 4 to 20 mA
S 19
2
y
R
(FE6) to AE2
S 67
2
Display y
R
Structure switch for the alarm settings:
S 76
0
Release for BA1
S 77
0
Release for BA2
S 80
1
A1 to BA1
S 81
2
A2 to BA2
S 94
38
A1 to
j
xd
j
S 96
2
A1 max / A2 max
S 267
1
A2 to x
Parameter oFPA
Para-
meters
Value
Meaning
dP1
*)
Decimal point
dA1
*)
Display start value
dE1
*)
Display full scale value
A1
5
Display full scale value
A2
70
Limit value
j
xd
j
Parameter onPA
para-
meters
Value
Meaning
Cp1
*)
Proport. action factor 1
tn1
*)
Integral action time 1
AH1
0.5
Response threshold
tY1
60 s
Runtime Drive
tA1
200
Factory setting
tA1
200
Factory setting
*) Setting as required
Содержание 6DR2210
Страница 2: ......
Страница 3: ...SIPART DR22 6DR2210 C79000 G7476 C154 03 1 SIPART DR22 6DR2210 Edition 12 2006 Manual ...
Страница 236: ...Manual 6 Ordering data 234 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 242: ...Manual 7 Application examples for configuring the controller 240 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 260: ...Manual 9 Explanation of abbreviations 258 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 268: ...Manual 266 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 269: ......