3 Operation
3.3 Configuring level (parameterization and structuring mode)
3.3.6 Structuring mode StrS (structure switches)
190
SIPART DR22 6DR2210
C79000-G7476-C154-03
Direction of effect of the digital inputs on assigned control signals
S39
CB/CB
ΙΙ
S40
He/He
ΙΙ
S41
N/N
ΙΙ
S42
Si/Si
ΙΙ
S43
P
Ι
/ P
ΙΙ
S44
+dw/--dw
S45
+dy/--dy
S46
+ybL/--ybL
+ybL
ΙΙ
/--ybL
ΙΙ
Direction
of effect
[ 0 ]
1
[ 0 ]
1
[ 0 ]
1
[ 0 ]
1
[ 0 ]
1
[ 0 ]
1
[ 0 ]
1
[ 0 ]
1
24 V = High
0 V = High
Direction of effect of the digital inputs BEs on bLS, bLPS and PAU corresponds to the meaning position ”0”.
Structure
switches
Switch
position
Function
p
uts
S47
[ 0 ]
1
2
Control signal CB
static without acknowledgement
static with acknowledgement
dynamic as pulse (flip-flop effect)
Dig
it
al
in
p
S48
[ 0 ]
1
Control signal N (follow-up)
static
dynamic as pulse (flip-flop effect)
S49
[ 0 ]
1
2
Blocking switching
Internal/External
internal only
external only
no blocking
sw
itc
hi
ng
S50
[ 0 ]
1
x-tracking at H + N (DDC) + Si
no
yes
set
p
o
in
t
sw
S51
[ 0 ]
1
setpoint in event of CB failure
last wi (at S52 = 0 last w)
safety setpoint SH
s
S52
[ 0 ]
1
Follow-up of wi to the
active setpoint
yes
no
S53
[ 0 ]
1
Source for the external setpoint
absolute setpoint WEA
incremental setpoint WE
∆
Structure
switches
Switch
position
Function
S54
[ 0 ]
1
Direction of effect of controller I
referenced to xd I
normal
(cP > 0)
reversed
(cP < 0)
thm
S55
[ 0 ]
1
2
3
D--element and z lock-on controller I
D-element
z
xd I
y
x I
y
Direction of effect
D-element (z(FE4))
against x
Direct. of effect with x D-element (z(FE4))
o
ntr
o
la
lgor
it
h
S56
[ 0 ]
1
Direction of effect controller II
referenced to xd II
normal
(cP > 0)
reversed
(cP < 0)
C
o
S57
[ 0 ]
1
2
3
D--element lock--on controller II
D-element
z
xd II
y
x II
y
Direction of effect
D-element (z(FE7))
against x
Direction of effect
D-element (z(FE7))
with x
S58
[ 0 ]
1
2
Adaptation selection
no adaptation possible
control behavior without overshoot
control behavior with periodic transient
response according to amount optimum
S59
[ 0 ]
1
2
Parameter control
without
Controller
I
(instead of parameter set
I
)
Controller
II
(instead of param. set
II
)
[
]
factory setting
Table 3--8 Structure switch tables (continued)
Содержание 6DR2210
Страница 2: ......
Страница 3: ...SIPART DR22 6DR2210 C79000 G7476 C154 03 1 SIPART DR22 6DR2210 Edition 12 2006 Manual ...
Страница 236: ...Manual 6 Ordering data 234 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 242: ...Manual 7 Application examples for configuring the controller 240 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 260: ...Manual 9 Explanation of abbreviations 258 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 268: ...Manual 266 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 269: ......