Manual
3 Operation
3.3
Configuring level (parameterization and structuring mode)
3.3.6 Structuring mode StrS (structure switches)
SIPART DR22 6DR2210
C79000-G7476-C154-03
187
Structure
switches
Switch
position
Function
S0
[ 0 ]
1)
1
↓
254
Identification of the user program
memory
s
Identification for factory setting (APSt)
ID number for various user programs
B
asic
set
ti
n
g
s
S1
[ 0 ]
1
2
3
4
5
6
7
8
9
10
11
12
Controller type
Fixed setpoint controller 2 independent
setpoints
Fixed setpoint controller 2 dependent
setpoints
DDC fixed setpoint controller
Follow-up/Synchronized/SPC controller
with Int/Ext switching
ratio controller
cascade control
ratio-cascade control
override control max. selection y
override control min. selection y
Process display
Fixed setpoint controller with 1 setpoint
(control system coupling)
Follow-up controller without Int/Ext
switching (control system coupling)
Double fixed setpoint/follow-up
controller
S2
[ 0 ]
1
2
Output structure
K-output
S-output internal feedback
S-output external feedback
in
p
u
ts
S3
[ 0 ]
1
Mains frequency suppression
50 Hz
60 Hz
An
al
o
g
i
S4
[ 0 ]
1
Connection of input range
fixed connection
free connection
S5
[ 0 ]
1
2
3
Input signal AE1
0 . . . 20 mA without
0 . . . 20 mA with
4 . . . 20 mA without
4 . . . 20 mA with
}
transmitter
monitoring
MUF
S6
[ 0 ]
1
2
3
Input signal AE2
0 . . . 20 mA without
0 . . . 20 mA with
4 . . . 20 mA without
4 . . . 20 mA with
}
transmitter
monitoring
MUF
[
]
factory setting
1)
Position 0 cannot be set manually.
As soon as the factory setting is changed (parameters or structures) S0 is automatically set from 0 to 1, APSt sets S0 to 0, FPSt has no
influence.
Table 3-8
Structure switch tables
Содержание 6DR2210
Страница 2: ......
Страница 3: ...SIPART DR22 6DR2210 C79000 G7476 C154 03 1 SIPART DR22 6DR2210 Edition 12 2006 Manual ...
Страница 236: ...Manual 6 Ordering data 234 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 242: ...Manual 7 Application examples for configuring the controller 240 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 260: ...Manual 9 Explanation of abbreviations 258 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 268: ...Manual 266 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 269: ......