Manual
2 Installation
2.2 Electrical Connection
2.2.3 Alternative connection for
I
- and U-input
158
SIPART DR22 6DR2210
C79000-G7476-C154-03
D
6DR2804-8A (interface relay 230 V, 4 relays)
6DR2804-8B (interface relay 230 V, 2 relays)
E.g. connection for
Δ
y outputs in the S controller with interface relay 230 V, 2 relays
(6DR2804-8B)
1/10
420 V
420 V
M
BA7
+
Δ
y
BA8
--
Δ
y
220
Ω
33n
1/1
1/11
220
Ω
33n
N
L
7/1
7/2
7/3
7/6
7/4
7/5
7/9
7/7
7/8
M
Figure 2-25
Connection of interface relay 230 V 6DR2804-8B
The interface relay 230 V, 4 relays (6DR2804-8A) contains 4 relays. Terminals 8/1 to 8/9 must
then be connected accordingly in addition to the terminals 7/1 to 7/8.
Attention:
Observe the max. switching voltage! (excessive increases in resonance in phase
shift motors, see chapter 1.4.2, page 13)
AC
250
8
1,250
V
A
VA
DC
250
8
30
100
V
A
W at 250 V
W at 24 V
2.2.3
Alternative connection for
I
- and U-input
D
0/4 to 20 mA signals
The 49.9
Ω
input impedance is connected across the input signals AE+ and AE- (AE1 to
AE3 in the standard controller and in module 6DR2800-8A by means of jumper settings and
by external wiring on the option module for AE4 and AE5).
If the signal is still required during service work in which the terminal is disconnected, the
input 49.9
Ω
input impedance
0.1 % must be connected to the terminal between AE+ and
AE--. The internal 49.9
Ω
resistance must then be disconnected by appropriate jumper
settings or by rewiring.
Содержание 6DR2210
Страница 2: ......
Страница 3: ...SIPART DR22 6DR2210 C79000 G7476 C154 03 1 SIPART DR22 6DR2210 Edition 12 2006 Manual ...
Страница 236: ...Manual 6 Ordering data 234 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...