Manual
3 Operation
3.3 Configuring level (parameterization and structuring mode)
3.3.6 Structuring mode StrS (structure switches)
198
SIPART DR22 6DR2210
C79000-G7476-C154-03
Structure
switches
Switch
posi-
tion
Function
S231
[ 0 ]
1
2
Output structure controller 2
K-output
S-output internal feedback
S-output external feedback
S232
[ 0 ]
1
2
Blocking switching
Internal/External controller 2 at
S1 = 12
internal only
external only
no blocking
S233
[ 0 ]
1
x-tracking controller 2 at
H+N(DDC)+Si
no
yes
S234
[ 0 ]
1
Setpoint at CB II failure
wi
we or last wes
S235
[ 0 ]
1
Follow-up wi II to active
setpoint
yes
no
S236
[ 0 ]
1
2
Display switching at
ratio controller/cascade
xv, wv / xv, wve
xv, wv / x, w (standardized to Ad, Ed)
xv, wv / x, wve / x, w
(standardized to Ad,
Ed)
S237
unused
Structure
switches
Switch
posi-
tion
Function
S238
[ 0 ]
1
priority N
II
(DDC) or H
II
N
II
+ (DDC)
H
II
S239
[ 0 ]
1
2
Manual operation controller
II
in case of transmitter fault
no switching
manual operation starting with last y
II
manual operation starting with yS
II
S240
[ 0 ]
1
2
3
4
Switching manual/automatic
controller
II
via
Manual key Hi control s. He
interlock He
ES
yes
yes/static
with
no
yes/static
with
no switching manual operation
yes
yes/dynamic
with
yes
yes/dynamic
without
sw
itc
hi
ng
S241
[ 0 ]
1
Function split range controller 2
(only K controller)
y3 rising / y4 falling
y1 rising / y4 rising
output
sw
S242
[ 0 ]
1
Iy switch off in N II/DDC II mode
(only K controller)
without
with
S243
[ 0 ]
1
2
oFF
Manipulated variable display
controller 2
controller output y
II
split range outputs y3/y4
position feedback y
R
II
no display
S244
[ 0 ]
1
Direction of effect manipulated
variable display controller 2
normal:
yAn = y
II
inverted:
yAn = 100 % -- y
II
S245
[ 0 ]
1
Manipulated variable limit YA/YE
only active in automatic operation
active in all operating modes
S246
[ 0 ]
1
Manipulated variable limit YA
II
/YE
II
only active in automatic operation
active in all operating modes
S247
[ 0 ]
1
Output signal AA5
0 to 20 mA
4 to 20 mA
p
uts
S248
[ 0 ]
1
Output signal AA6
0 to 20 mA
4 to 20 mA
n
al
og
outp
u
S249
[ 0 ]
1
Output signal AA7
0 to 20 mA
4 to 20 mA
an
a
S250
[ 0 ]
1
Output signal AA8
0 to 20 mA
4 to 20 mA
S251
[ 0 ]
1
Output signal AA9
0 to 20 mA
4 to 20 mA
[
]
factory setting
Table 3--8 Structure switch tables (continued)
Содержание 6DR2210
Страница 2: ......
Страница 3: ...SIPART DR22 6DR2210 C79000 G7476 C154 03 1 SIPART DR22 6DR2210 Edition 12 2006 Manual ...
Страница 236: ...Manual 6 Ordering data 234 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 242: ...Manual 7 Application examples for configuring the controller 240 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 260: ...Manual 9 Explanation of abbreviations 258 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 268: ...Manual 266 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 269: ......