Manual
2 Installation
2.1 Mechanical Installation
SIPART DR22 6DR2210
C79000-G7476-C154-03
143
2
Installation
2.1
Mechanical Installation
D
Selecting the Installation Site
Maintain an ambient temperature of 0 to 50
_
C. Don’t forget to allow for other heat sources
in the vicinity. Remember that if instruments are stacked on top of each other with little or no
gap between them, additional heat will be generated. Front and rear sides of the controller
must be easily accessible.
D
Panel mounting
The SIPART DR22 is installed either in individual panel cutouts or in open tiers (for dimen-
sioned diagram, see chapter 1.6.1, page 128 fig. 1-72, and fig. 1-73).
-- The upper edge of the panel cut-out must be left unpainted to ensure good interference
suppression of the controller even at high frequencies. A good HF ground connection is
established by the contact spring protruding from the top of the SIPART DR22.
-- If necessary: Push self-adhesive sealing ring for sealing front frame/front panel over the
tube and stick to the tube collar (see chapter 5.2, page 231, item 2.6).
-- Insert SIPART DR22 into the panel cut-out or open tier from the front and fit the two
clamps provided to the controller unit from the rear so that they snap into the cut-outs in
the casing.
-- Align SIPART DR22 and do not tighten the locking screws too tight. The tightening range
is 0 to 40 mm.
2.2
Electrical Connection
The arrangement of the connecting elements can be seen in fig. 2-1, page 145.
!
WARNING
The ”Regulations for the installation of power systems with rated
voltages under 1000 V” (VDE 0100) must be observed in the electrical
installation!
D
PE conductor connection
Connect the PE conductor to the ground screw (see figure 2-1) on the back of the controller.
When connecting to 115 or 230 V AC mains supply, the PE conductor can also be con-
nected through the three-pin plug (see figure 2-1). The controller’s ground connection may
also be connected with the PE conductor (grounded extra low voltages).
Содержание 6DR2210
Страница 2: ......
Страница 3: ...SIPART DR22 6DR2210 C79000 G7476 C154 03 1 SIPART DR22 6DR2210 Edition 12 2006 Manual ...
Страница 236: ...Manual 6 Ordering data 234 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 242: ...Manual 7 Application examples for configuring the controller 240 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 260: ...Manual 9 Explanation of abbreviations 258 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 268: ...Manual 266 SIPART DR22 6DR2210 C79000 G7476 C154 03 ...
Страница 269: ......