Manual
2 Installation
2.2 Electrical Connection
2.2.1 Connection standard controller
SIPART DR22 6DR2210
C79000-G7476-C154-03
147
2.2.1
Connection standard controller
D
Power supply connection
Attention:
Set mains voltage selection switch (see fig. 2-1) in no-voltage state according to the
available mains voltage!
-- 6DR2210-5
115/230 V AC, switchable
Three-pin plug IEC 320 IV
DIN 49457A
1 A slow blow per controller
L N PE
230
115
~
=
+ 24 V
+ 5 V
U
REF
other loads on the same
signal loop; use larger
fuse if necessary
Alternative
DR 22
6DR2210-5
115 or 230 V AC
L
N
PE
Figure 2-3
Connection 115/230 V AC power supply
-- 6DR2210-4
24V UC
Special 2-pin plug
any polarity
=
other loads on the same
signal loop; use larger
fuse if necessary
DR 22
6DR2210-4
3.15 A slow blow per controller
24 V UC
+ 24 V
+ 5 V
U
REF
Figure 2-4
Connection 24 V DC power supply