8. Program the input terminals X3:42, X3:43 and X3:47.
9. Set the rapid stop ramp, as the drive is decelerated along the rapid stop ramp in case of a bus
fault.
10.Set the inverter control mode parameter at Fieldbus.
11.Set the machine parameters for IPOS according to your application.
12.The position setpoint specified via fieldbus, in this application example, is to be used in the
automatic program of the inverter with the command
GOPA. Therefore set the IPOS-bus mode = 2.
13.Set the reference travel to type 3 (= limit switch CW).
14.Now write the IPOS automatic program and use the command
GOPA, in order to be able to
implement the position setpoint of the fieldbus. Fig. 74 shows the minimum program for the use
of the position setpoint of the fieldbus interface.
602 NO FUNCTION
TERMINAL 47
601 /LIMIT SWITCH CCW
TERMINAL 43
600 /LIMIT SWITCH CW
TERMINAL 42
01153AEN
Fig. 71: Programming of the terminals X3:42, X3:43 and X3:47
140 T13 0.20 s
STOP RAMP
00353AEN
Fig. 72: Programming of the ramp generator used by this application program
841 FIELDBUS
CONTROL MODE
00343AEN
Fig. 73: Switching to control mode fieldbus using keypad
7
Application Examples
MOVITRAC
®
31.. Fieldbus Unit Profile