3. Activate the factory setting.
4. Set the inverter control mode parameter at Fieldbus
5. The process data-description parameters PO1, PI1, PO2 and PI2 are changed according to the
application specification.
6. As the setpoint description for the process input data has been changed, the inverter has locked
automatically with
enable fieldbus setpoints = NO. Re-enable the fieldbus setpoints with P570
enable fieldbus setpoints = YES.
7. Program the fieldbus parameter
Fieldbus Timeout to 100 ms and the parameter Timeout
Response to Rapid Stop as set out in the objective.
830 YES
FACTORY SETTING
00342AEN
Fig. 66: Activating the factory setting via the keypad
841 FIELDBUS
CONTROL MODE
00343AEN
Fig. 67: Switching to control mode fieldbus using keypad
561 STATUS WORD 2
setpoint description PI1
563 POSITION HIGH
actual value description PI2
565 POSITION LOW
setpoint description PI3
560 STATUS WORD 2
setpoint description PO1
562 POSITION HIGH
setpoint description PO2
564 POSITION LOW
setpoint description PO3
01151AEN
Fig. 68: Programming of the process data-description parameters via keypad
570 YES
ENABLE SETPOINTS
00352AEN
Fig. 69: Enabling fieldbus setpoints via keypad
572 RAPID STOP
TIME OUT RESPONSE
571 0.10 s
FIELDBUS TIME OUT
00345AEN
Fig. 70: Programming the fieldbus timeout and timeout response via keypad
Application Examples
7
74
MOVITRAC
®
31.. Fieldbus Unit Profile