6. Program the input terminals 42 and 43 to NO FUNCTION to enable the inverter on the terminal
side via the jumper (installed before).
7. Program the fieldbus parameter
Fieldbus Timeout to 100 ms and the parameter Timeout
Response to Rapid Stop as set out in the Objective.
8. Now enter all parameters specific to the drive, such as motor parameters, frequency
characteristics, etc. (
→
MOVITRAC
®
31.. Installation and Operating Instructions).
9. Enter the ramp generators for the acceleration, deceleration and rapid stop ramps. As the first
parameter set and the first ramp generator set of it are to be used, the ramp generators
T11 Ramp
Up, T11 Ramp Down and T13 Stop Ramp must be changed.
All the parameters for this application example have now been assigned.
601 NO FUNCTION
TERMINAL 43
600 NO FUNCTION
TERMINAL 42
00344AEN
Fig. 37: Programming terminals 42 and 43 from the keypad
572 RAPID STOP
TIME OUT RESPONSE
571 0.10 s
FIELDBUS TIME OUT
00345AEN
Fig. 38: Programming the fieldbus timeout and timeout response from the keypad
120 T11 1.50 s
RAMP UP
121 T11 2.00 s
RAMP DOWN
140 T13 0.20 s
STOP RAMP
00346AEN
Fig. 39: Programming the ramp generators used in the application program
7
Application Examples
MOVITRAC
®
31.. Fieldbus Unit Profile
59