7
Application Examples
This section gives two examples of applications that demonstrate how to operate the MOVITRAC
®
31.. inverter with a fieldbus connection and control it via the fieldbus option pcb.
7.1
Control Using Two Process Data Words
This example uses the process data description parameters
P560
PO1 Setpoint Description:
Control Word 1
P561
PI1 Actual Value Description: Status Word 1
P562
PO2 Setpoint Description
Speed Setpoint
P563
PI2 Actual Value Description Speed Actual Value
P564
PO3 Setpoint Description
No Function
P565
PI3 Actual Value Description No Function
valid after a factory setting has been carried out.
This configuration allows you to implement a broad range of applications without having to change
the process data assignment. Fig. 33 shows the process data transmitted between the control unit
and the inverter.
7.1.1
Objective
The inverter is to be controlled by means of two process data words. The process output data
Control
Word 1 and Speed Setpoint are to be specified by the higher-level control unit. Conversely, the
inverter is to return the process input data
Status Word 1 and Speed Actual Value to the higher-level
control unit.
The application program is to control the following inverter functions:
1) The digital input E1.1 is to trigger the control commands
Enable and Stop.
E1.1 = 1: Enable
E1.1 = 0: Stop
2) The digital input E1.2 is to trigger the control commands
Enable and Rapid Stop.
E1.2 = 1: Enable
E1.2 = 0: Rapid stop
3) The digital input E1.3 is to specify the speed setpoint.
E1.3 = 1: 750 1/min CCW
E1.3 = 0: 1000 1/min CW
M
O
VI
TRAC
®
841
E
Q
RUN
BUS
FAULT
FIELDBUS
CONTROL MODE
Status
word 1
Speed
actual value
Speed
setpoint
Control
word 1
Process input data (PI)
Process output data (PO)
00340AEN
Fig. 33: Application example for inverter control using two process data words
7
Application Examples
MOVITRAC
®
31.. Fieldbus Unit Profile