4. Set the inverter control mode parameter at Fieldbus.
5. The process data-description parameters PO1, PI1, PO2 and PI2 are changed according to the
application specification.
6. As the setpoint description for the process input data has been changed, the inverter has locked
automatically with
enable fieldbus setpoints = NO. Re-enable the fieldbus setpoints with P570
enable fieldbus setpoints = YES.
7. Program the input terminals 42 ... 50 to NO FUNCTION, so that the inverter is enabled on the
terminal side via the previously inserted jumper and ignores the sensor/actor signals of the input
terminals during drive control.
841 FIELDBUS
CONTROL MODE
00343AEN
Fig. 53: Switching to control mode fieldbus using keypad
561 STATUS WORD 2
actual value description PI1
562 SPEED [%]
setpoint description PO2
563 SPEED [%]
actual value description PI2
560 STATUS WORD 2
setpoint description PO1
01141AEN
Fig. 54: Programming of the process data description parameters via keypad
570 YES
ENABLE SETPOINTS
00352AEN
Fig. 55: Enabling fieldbus setpoints via keypad
601 NO FUNCTION
TERMINAL 43
603 NO FUNCTION
TERMINAL 48
605 NO FUNCTION
TERMINAL 50
600 NO FUNCTION
TERMINAL 42
602 NO FUNCTION
TERMINAL 47
604 NO FUNCTION
TERMINAL 49
01142AEN
Fig. 56: Programming of the terminals 42 ... 50 via keypad
Application Examples
7
68
MOVITRAC
®
31.. Fieldbus Unit Profile