9.3
MOVIFIT
®
compact reversing starter
MOVIFIT®
compact
reversing
starter
MOVIFIT
®
compact type
MBS2RB-..
MBS4RB-..
Connection voltages
V
line
3 × AC 380 V –10% – AC 500 V +10%
Line frequency
f
line
50 – 60 Hz ±5%
Output voltage
V
O
V
line
The motor output is not short-circuit-proof.
Notice: Dangerous contact voltages. The motor
output is switched using semiconductors.
Output frequency
f
A
f
line
Nominal output current
I
N
AC 5.0 A
AC 10.0 A
Motor power S1
(with V
line
= 400 V)
P
Mot
0.18 –
2.2 kW
0.24 – 3.0 HP
2.2 –
4.0 kW
3.0 – 5.4 HP
Device variant
1
Utilization category
5A:AC-53b:5-2:10
10 A:AC-53b:4-2:10
According to EN 60947-4-2:2012
Rated insulation voltage
500 V
Rated insulation surge
voltage
4 kV
Start-up type
Voltage ramp, current limiting, boost
Starting voltages
40 – 80%
Current limiting
100 – 500%
Boost
60 – 100% for 100 – 2000 ms
Soft start/braking time
0 – 2 s
Repeat readiness
50 ms
Switching frequency
Max. 300 switching operations per hour
Switching frequency (by-
pass deactivated)
Max. 3000 switching operations per hour
I
2
t power semiconductor
390 A
2
s
Efficiency
> 95%
With increased switching operation, the effi-
ciency can be < 95%.
Maximum motor cable
length
10 m unshielded
Permitted motors
Asynchronous motors
Interference immunity
Fulfills EN 60947-4-2:2012
Interference emission
Fulfills class B in accordance with
EN 60947-4-2:2012
Ambient temperature
ϑ
A
-20 °C – +40 °C
P
N
reduction: by 3% per K up to max. 60 °C
Climate class
EN 60721-3-3, class 3K3
22527060/EN – 08/2017