6
Startup
Parameter list for the MOVIFIT® compact motor starter
Operating Instructions – MOVIFIT
®
compact
71
Parameter index 10546.215/10546.216
Boost mode, drive 1/2
Range of values:
Off
, on
Boost mode can be activated if an increased breakaway torque is required.
If boost mode is activated, the motor is activated with the boost voltage U
B
after en-
abling before the soft start begins. After the boost time t
B
has elapsed, the soft start
phase commences with the parameterized starting voltage U
s
.
t
U
M
U
B
t
U
t
B
18512872459
U
M
Motor voltage
U
B
Boost voltage
t
B
Boost duration
t
U
Soft start time
Parameter index 10546.217/10546.218
Boost voltage, drive 1/2
Range of values: 60 –
80
– 100% of nominal motor voltage
The boost voltage U
B
is the motor voltage increase during the boost time t
B
.
Parameter index 10546.219/10546.220
Boost duration, drive 1/2
Range of values: 0.1 –
0.5
– 2 s
The boost time t
B
is the duration for which the boost voltage is active.