6
Startup
Functions of the MOVIFIT® compact with binary control
Operating Instructions – MOVIFIT
®
compact
74
6.11
Functions of the MOVIFIT
®
compact with binary control
Functions
of the
MOVIFIT®
compact
with binary
control
6.11.1
PLC → MOVIFIT
®
compact data transmission
MOVIFIT
®
compact inverter
The following table shows the control signals that the higher-level controller transmits
to the MOVIFIT
®
compact inverter and the functions of the drive:
Control signals
Function
DI03 DI02 DI01 DI00
MOVIFIT
®
compact inverter
X
X
0
0
Stop
X
X
0
1
Enable CW rotation
X
X
1
0
Enable CCW rotation
X
X
1
1
Stop/reset
0
0
X
X
Setpoint speed = n1
0
1
X
X
Setpoint speed = n2
1
0
X
X
Setpoint speed = n3
1
1
X
X
Setpoint speed = n4
MOVIFIT
®
compact reversing and dual-motor starter (default mode,
P-600
= 0)
The following table shows the control signals that the higher-level controller transmits
to the MOVIFIT
®
compact motor starter and the functions of the drive:
Control signals
Function
DI02 DI01 DI00
MOVIFIT
®
compact
reversing starter
MOVIFIT
®
compact
dual-motor starter
0
0
0
Stop
Stop
0
0
1
Enable CW rotation
Enable signal motor 1 at connect. X9
0
1
0
Enable CCW rotation
Enable signal motor 2 at connect. X8
0
1
1
Stop
Enable signal motors at X9 + X8
1
X
X
Reset
Reset
MOVIFIT
®
compact reversing starter (alternative mode,
P-600
= 1)
The following table shows the control signals that the higher-level controller transmits
to the MOVIFIT
®
compact reversing starter
in alternative mode
(
P-600
= 1) and the
functions of the drive:
Control signals
Function
DI02 DI01 DI00
MOVIFIT
®
compact reversing starter
X
0
0
Stop
X
0
1
Enable CW rotation
X
1
0
Enable CCW rotation
X
1
1
Reset
X = any status
22527060/EN – 08/2017