5
Electrical installation
Motor connection
Operating Instructions – MOVIFIT
®
compact
32
5.6.2
X9, (X8): Motor connection
Plug connector X8 is only present on the MOVIFIT
®
compact dual-motor starter.
Connection
The following table provides information about this connection:
Function
Power connection for motor with brake
Connection type
Q 8/0, female
Connection image
8
5
3
1
2
4
PE
6
7
No.
Name
Function
1
U
Motor phase U output
2
n. c.
Not connected
3
W
Motor phase W output
4
L1
Supply of mechanical brake
(Only with MOVIFIT® compact inverter)
5
n. c.
Not connected
6
L2_S
Supply of mechanical brake switched
(Only with MOVIFIT® compact inverter)
7
V
Motor phase V output
8
n. c.
Not connected
PE
PE
Protective earth
Connection cable
The following table shows possible motor cables:
NOTICE
Danger due to short circuit. The motor outputs of the MOVIFIT
®
compact motor
starter are not protected against short circuits.
MOVIFIT
®
compact motor starter is destroyed.
•
Observe the following wiring diagrams.
•
Prevent any short circuits between the conductors.