6
Startup
Startup procedure for MOVIFIT® compact inverter
Operating Instructions – MOVIFIT
®
compact
46
Parameters for PROFI mode
(with 4-pole non-SEW motors)
Non-SEW motor
Size
Setting on the
MBBG11A
op-
erator panel
Parameter
in MOVITOOLS
®
MotionStudio
Grou
p
Parameter
Nominal motor voltage
UoLt
3
Nominal voltage
Nominal motor power
PoUEr
3
Nominal power
Nominal motor current
AMPEr
3
Nominal motor current
Rated motor frequency
hErtZ
3
Nominal frequency
Nominal motor speed
rPN
3
Nominal speed
"Commence motor
startup" function
CALC = St
Art
3
Commence motor start-
up
= Yes
1)
Acceleration ramp
1
P-130 Ramp up
Deceleration ramp
1
P-131
Ramp down
Setpoint speed n1
xx
n
n1
1
P-170 fixed setpoint n1
Setpoint speed n2
n2
1
P-171 fixed setpoint n2
Setpoint speed n3
n3
1
P-172 fixed setpoint n3
Setpoint speed n4
n4
1
P-173 fixed setpoint n4
In order to operate with LVFC control, the following parameters are also required:
Operating mode
ModE = L
VFC
7
P-700 operating mode
= LVFC
1) Click on the [Commence startup] button in MOVITOOLS® MotionStudio.
6.
NOTICE!
Loss of the ensured degree of protection if the screw plug is not installed
or not installed correctly on the diagnostic interface. Damage to the MOVIFIT
®
compact device.
Make sure the screw plug of the diagnostic interface has a seal and screw it in.
7. Switch off the line voltage.
8. Set the AS-Interface slave address of the MOVIFIT
®
compact device (only
with MOVIFIT
®
compact with AS-Interface).
ð
See chapter "Assigning the AS-Interface slave address".
9. Start up the higher-level controller.
10. Connect the plug of the motor to the MOVIFIT
®
compact.
11. Switch on the line voltage.
The MOVIFIT
®
compact drive can now be controlled using the higher-level controller
(binary signals or via AS-Interface).
22527060/EN – 08/2017