6
Startup
Startup procedure for MOVIFIT® compact motor starter
Operating Instructions – MOVIFIT
®
compact
49
6.4.2
Parameters for “Current limiting” operating mode
Description
When the drive starts, the MOVIFIT
®
compact motor starter imposes the current I
e
into
the motor. The current I
e
is defined with parameter
P13 Current limit
. The motor accel-
erates depending on the motor current I
M
.
Time t
I
is used to monitor the starting procedure. Within the monitoring time t
I
, the mo-
tor current must have left its increased startup value and have dropped to the nominal
current or below. If the motor is still carrying a current that is greater than the nominal
motor current after monitoring time t
I
, the MOVIFIT
®
compact motor starter switches to
fault condition F 34 (Start time monitoring error); see chapter "MOVIFIT
®
compact mo-
tor starter error list" (→
89).
t
I
M
I
e
t
I
Parameter
In order to start up in “Current limiting” operating mode, set the following parameters:
“Current limiting” operating mode
Size
Setting on the MB-
BG11A
operator panel
Parameter
in MOVITOOLS
®
MotionStudio
Grou
p
Parameter
Start mode
Par
P-01 drive 1 = 1
7
Start mode drive 1
= current
limited
P-02 drive 2
1)
= 1
7
Drive 2 start mode
= Current-
limited
1)
Nominal motor cur-
rent
P-03 drive 1
3
Nominal motor current drive 1
P-04 drive 2
1)
3
Nominal motor current drive 2
1)
Current limit I
e
P-13 drive 1
3
Current limit drive 1
P-14 drive 2
1)
3
Current limit drive 2
1)
Monitoring time t
I
start phase
P-09 drive 1
5
Monitoring time for start phase
drive 1
P-10 drive 2
1)
Monitoring time for start phase
drive 2
1)
1) Only with dual-motor starter