6
Startup
Startup procedure for MOVIFIT® compact motor starter
Operating Instructions – MOVIFIT
®
compact
48
6.4.1
Parameters for “Voltage limitation” operating mode
Description
The MOVIFIT
®
compact motor starter increases the motor voltage along a ramp within
the set time t
U
= 0 ‑ 2 s up to the nominal value.
The starting voltage at which the acceleration procedure begins can be set within the
limits U
S
= 40 – 80% of the motor voltage U
M
via the parameters
Start voltage drive 1
or
Start voltage drive 2
.
t
U
M
U
S
t
U
When you cancel the enable, the MOVIFIT
®
compact motor starter reduces the motor
voltage along a ramp within the set braking time.
Parameter
In order to start up in “Voltage limitation” operating mode, set the following paramet-
ers:
“Voltage limiting” operating mode
Size
Setting on the MB-
BG11A
operator panel
Parameter
in MOVITOOLS
®
MotionStudio
Grou
p
Parameter
Start mode
Par
P-01 drive 1 = 0
7
Start mode drive 1
= Voltage-
limited
P-02 drive 2
1)
= 0
7
Start mode drive 2
= Voltage-
limited
1)
Nominal motor cur-
rent
P-03 drive 1
3
Nominal motor current drive 1
P-04 drive 2
1)
3
Nominal motor current drive 2
1)
Soft start t
U
P-05 drive 1
1
P-130 soft start time drive 1
P-06 drive 2
1)
1
P-131 soft start time drive 2
1)
Braking time
P-07 drive 1
1
Braking time drive 1
P-08 drive 2
1)
1
Braking time drive 2
1)
Start voltage U
S
P-11 drive 1
3
Starting voltage drive 1
P-12 drive 2
1)
3
Start voltage drive 2
1)
1) Only with dual-motor starter
22527060/EN – 08/2017