Startup
Startup procedure for MOVIFIT® compact inverter
Operating Instructions – MOVIFIT
®
compact
45
6.3
Startup procedure for MOVIFIT
®
compact inverter
Startup
procedure
for
MOVIFIT®
compact
inverter
To start up the inverter, proceed as follows:
1. Check the connection of the MOVIFIT
®
compact device.
ð
See chapter "Electrical installation".
2. Ensure that the motor does not start up, and that there is no hazard from an un-
wanted motor startup.
3. Switch on the line voltage. The “STATUS” LED illuminates in yellow.
4. Connect the MBBG11A operator panel or PC/laptop to the MOVIFIT
®
compact
device.
ð
See chapter "Connecting the MBBG11A operator panel"
ð
or chapter "Connecting a PC/laptop".
There are two ways of starting up the inverter:
•
Use Easy mode for a quick startup of SEW‑EURODRIVE motors.
•
Use PROFI mode to start up third-party motors. The system requires more data to
start up third-party motors.
5. To start up in Easy mode, set the following parameters on the MBBG11A operator
55)) or on the PC/laptop (see (→
ð
The parameter list can be found in chapter
"
61).
Parameters for Easy mode
(with 4-pole SEW-EURODRIVE motors)
SEW-EURODRIVE motor
Size
Setting on the
MBBG11A
op-
erator panel
Parameter
in MOVITOOLS
®
MotionStudio
Grou
p
Parameter
Startup mode
EASY
3
Startup
= EASY
Nominal motor voltage
UoLt
3
Nominal voltage
Nominal motor power
PoUEr
3
Nominal power
"Commence motor
startup" function
CALC = St
Art
3
Commence motor start-
up
= Yes
1)
Acceleration ramp
1
P-130 Ramp up
Deceleration ramp
1
P-131
Ramp down
Setpoint speed n1
xx
n
n1
1
P-170 fixed setpoint n1
Setpoint speed n2
n2
1
P-171 fixed setpoint n2
Setpoint speed n3
n3
1
P-172 fixed setpoint n3
Setpoint speed n4
n4
1
P-173 fixed setpoint n4
In order to operate with LVFC control, the following parameters are also required:
Operating mode
ModE = L
VFC
7
P-700 operating mode
= LVFC
1) Click on the [Commence startup] button in MOVITOOLS® MotionStudio.
22527060/EN – 08/2017