Manual – MOVI-PLC® Application Solution "SyncCrane"
5
Drive inverter parameters
Startup
5.5
Drive inverter parameters
The following parameters are written to the drive inverter each time the startup wizard
is opened or the program is started:
5.6
Group signals
5.6.1
Bit-coded representation
Group signals are displayed in bit code.
The group signal makes the following possible:
• Evaluating the status of the individual axes by interpreting the logical axis address
• Querying the status of the entire axis system by interpreting the group signal (bit "0")
For example, the "InGear" signal would be displayed as follows:
Parameter number
Index
Description
Setting
350
8537
Motor direction of rota-
tion
Normal/inverted
945
8891
Encoder type
Ext. Encoder
950
8777
Encoder type DIP
Ext. DIP encoder
946
8894
Counting direction
Ext. Encoder
951
8776
Counting direction
Ext. DIP encoder
944
8787
Scaling factor
Ext. Encoder
955
8784
Scaling factor
Ext. DIP encoder
302
8517
Max. motor speed
Motor parameters
971
9226
Synchronization phase
–
536597259
Bit 0 True= Axis1 InGear AND Axis2 InGear AND....
Bit 1 Axis LogAdr 1 "InGear"
Bit 2 Axis LogAdr 2 "InGear"
Bit 3 Axis LogAdr 3 "InGear"
Bit 4 Axis LogAdr 4 "InGear"
Bit 5
Bit 6
Bit 7
0
0
I