Annex
Operating Manual XCA 1100 / XCA 1200
●
Version 12/17
147
14
Annex
14.1
Technical Data of all Modules
Climatic conditions
Ambient operating temperature
0 ... +55°C (category KV to DIN 40040),
vertical installation, free air circulation
Storage temperature
-25 ... +70°C (category HS to DIN 40040)
Relative humidity
10 ... 95% (category F to DIN 40040), no
condensation
Air pressure in operation
860 ... 1060 hPa
Mechanical strength
Vibration
Acc. to DIN EN 60068-2-6
10 ... 57 Hz constant amplitude 0.075mm
57 ... 150 Hz constant acceleration 1 g
Shock
Acc. to DIN EN 60068-2-27,
sinusoidal half-wave 15g / 11 ms
Free fall
Acc. to DIN EN 60068-2-32,
fall height 1m (with original packaging)
Electrical safety
Protection class
Class I, basic insulation and
PE terminal (to IEC 60536)
Protection type
IP 00 to EN 60529
Clearance/creepage distance
DIN EN 61131-2
between electrical circuits and objects as well as
between decoupled electrical circuits,
corresponding to
overload category II, contamination level 2
Test voltage
AC 350 V/50Hz for device rated voltage DC 24V
AC 1350 V/50Hz for device rated voltage AC 230V
Electromagnetic compatibility
Electrostatic discharge
EN 61000-4-2:
8 KV air discharge,
4kV contact discharge
Electromagnetic fields
EN 61000-4-3,
field intensity 10 V/m, 80 ... 1000 MHz
Rapid transients (bursts)
EN 61000-4-4: 2kV
on DC supply lines
,
1kV on I/O signal lines
Interference emissions
EN 55011,
limit category A, Group 1