Commissioning
Operating Manual XCA 1100 / XCA 1200
●
Version 12/17
59
The
Module properties
dialog window is then called via the
Properties
button for each of the two new modules (
Figure46:
"XUIO configuration"
dialog window,
properties
The
Option
setting in the
Module properties
dialog is set to 1 for both
modules (
Figure47). A total of 32 options 0...31 can be set. All
other modules retain their setting. The preset is option 0.
Figure47:
"Module properties"
dialog window,
set options
Both UZB 2VR units belong to option 1, all other modules to option 0.
The saved hardware configuration is compared to the actual hardware
available when the controller starts up. Either all modules of an option
must be available (the option is then active), or no modules must be
available for this option (the option is then inactive). The address
ranges of inactive options are remain reserved.
If the modules of an option are only partly available, a configuration
error is detected. (BUS LED on the control unit flashes red and an
error message is saved in the active error buffer).