Commissioning
Operating Manual XCA 1100 / XCA 1200
●
Version 12/17
55
The saved hardware configuration is compared with the actual
hardware configuration available each time the controller is started. If
there any differences, the controller startup is interrupted with an error
message. The
BUS
LED on the control unit flashes red and an error
message is saved in the active error buffer:
0x01100001
Incompatible hardware configuration
The active error buffer and error log book can be viewed on each
operating level in the Schleicher dialog via the key combination
<Ctrl+?>.
The required entries in the I/O configuration for the created hardware
configuration are inserted in the PLC project (the I/O configuration can
be opened by double-clicking on the
IO_Configuration
node in the
project tree
Figure41:
"IO_Configuration" node