MODULAR SUNWAY TG
TE OD
INSTALLATION GUIDE
96/
139
Rev. 03
– 01/06//2018
Check control and auxiliary voltages (110 V and 24 V)
Every 6 months
Check fuses and disconnect switches
Every 6 months
Check SPDs
Every 6 months
Check that cables and bars are securely tightened
Every 12 months
Calibrate environmental sensors
Every 12 months
Check the condition of nameplate and warning signs
Every 24 months
The frequency of scheduled maintenance may need to be increased depending on the location in which
the equipment is installed and the relative ambient conditions.
Table 28: Maintenance Sheet
DC- Parallel Maintenance
Minimum Frequency
Check the DC-Parallel cables and bars are securely tightened
Every 12 months
Checking the fuse status switches on the DC-Parallel (if installed)
Every 12 months
Table 29: Integrated DC- Parallel Maintenance Sheet
10.2.
Reading the fault list archives
To guarantee correct operation of the system all its components must be correctly matched up. Incorrect
operation leads to lower yields with a subsequent reduction in system profitability.
The inverter includes functions to warn the user of failures or faults affecting the system. Periodical checks
of system operation are in any case still necessary for the detection of minor operating faults which are not
associated with an alarm. The inverter’s alarm memory and the data stored in the Data Logger (if installed)
must be analysed at least once a month. To do this, proceed as described in the Programming Guide.
10.3.
Checking the external and internal conditions
To check the external/internal conditions of the electrical cabinet, proceed as follows:
OVERALL CONDITION OF THE CABINET
•
Check the external condition of the cabinet.
•
Check the state of the isolating sheaths on the conductors.
•
Check that there are no signs of overheating on the power conductors (especially near the connection
points on the equipment).
•
Check that there are no signs of cable gnawing caused by rodents.
•
Check the state of all the signs/nameplates affixed to the equipment. Signs must always be in good
condition and legible.
GENERAL CABINET CLEANING
•
Check the interior of the cabinet for the build-up of dust, dirt, humidity and infiltration of water from
the outside.
•
Check that the ventilation ducts on the inductors and transformers are clear.