MODULAR SUNWAY TG
TE OD
INSTALLATION GUIDE
26/
139
Rev. 03
– 01/06//2018
4. PRODUCT CONFIGURATION
The SUNWAY TG TE models mentioned in section 1.1 may be made up of conversion modules functionally
independent of each other and able to operate in parallel with one or more units. Each product configuration
is typically composed of an AC module and a variable number of DC modules. The AC module is the point
of interconnection between the inverter and the grid and contains the output AC circuit breaker. The DC
modules perform DC/AC power conversion. They may operate either independently of each other by
implementing individual MPPTs, or in master-slave mode, by implementing a single MPPT.
The great number of combinations of the AC and DC modules and their operating modes results in a product
range with output power ratings from 600 kVA to 3200 kVA installed, applicable to multiple PV field
configurations, including the earthed field configurations.
The possible configurations are given in the section below. Please refer to section
Error! Reference source n
ot found.
for the technical specifications of each configuration.
4.1.
Inverter configuration
Single Converter
Configuration featuring
one single converter
AC
Modules
DC
Modules
MPPTs
1
1
1
Minimum configuration, with only one
converter and single MPPT. No
coordination is required.
Configuration featuring
dual converter, multi-master
AC
Modules
DC
Modules
MPPTs
1
2
2
Each DC module is connected to its
own
independent
field.
Each
conversion
module
operates
independently of each other and
performs the MPPT function. The
PV arrays may have different
features
and
installation
requirements.
Configuration featuring
dual converter,
single master