![Santerno SUNWAY TG1200 1000V TE OD Скачать руководство пользователя страница 95](http://html1.mh-extra.com/html/santerno/sunway-tg1200-1000v-te-od/sunway-tg1200-1000v-te-od_installation-manual_810313095.webp)
INSTALLATION GUIDE
MODULAR SUNWAY TG
TE OD
Rev. 03
– 01/06/2018
95/
139
10. MAINTENANCE
Adequate maintenance ensures conversion performance and inverter reliability is maintained over time.
This heading describes all the activities required to keep machine parts which are subject to wear and
deterioration and/or components which are essential for guaranteeing safety and optimum performance in
good condition.
Access to products for the purpose of maintenance, modifications and management involves all persons
responsible for production and maintenance. It must be carried out in observance of the health and safety
regulations described in section 2.5.
The minimum maintenance interval is indicated in section 10.1.
Equipment installed in an environment where there is a high concentration of dust requires more frequent
maintenance than generally indicated.
The activities described may involve stopping the inverter. Once the maintenance procedure has been
completed restart the inverter by pressing the START button.
WARNING
Failure to observe the maintenance prescriptions may result in the product warranty
conditions being nullified.
NOTE
In the event of any fault, please contact the Elettronica Santerno SpA CUSTOMER SERVICE
for instructions on the necessary corrective action to be taken.
WARNING
In case of long downtimes, run the inverter fans for 24h before restarting the product in
order to suppress condensation.
Please contact Elettronica Santerno SpA Customer Service for the necessary corrective
actions.
10.1.
Maintenance sheet
Maintenance tasks
Minimum Frequency
Read the stored data and Fault List
Every month
Checking the external/internal conditions of the electrical cabinet
Every 6 months
Air filter maintenance
Every 6 months
Check the emergency stop button
Every 12 months
Checking the door microswitches
Every 12 months
Check gaskets
Every 12 months
Check locks and hinges
Every 12 months
Check the fans
Every 6 months