![Santerno SUNWAY TG1200 1000V TE OD Скачать руководство пользователя страница 111](http://html1.mh-extra.com/html/santerno/sunway-tg1200-1000v-te-od/sunway-tg1200-1000v-te-od_installation-manual_810313111.webp)
INSTALLATION GUIDE
MODULAR SUNWAY TG
TE OD
Rev. 03
– 01/06/2018
111/
139
•
Make sure that key-operated selector switch 41SA1 is set to DISABLED.
•
Open the door on the DC section and remove the lower grille covering the base of the input fuse-
holder.
•
Remove the auxiliary contact kit from the damaged fuse.
•
Remove the faulty fuse using the special isolated handle provided.
•
Install a new fuse using the special isolated handle provided.
•
Reconnect the auxiliary contact kit to the new fuse.
•
Reassemble the protective grille.
Figure 71: Extracting the fuse: disconnection of a microswitch and handle for removing the fuse