MODULAR SUNWAY TG
TE OD
INSTALLATION GUIDE
74/
139
Rev. 03
– 01/06//2018
•
Check that the key-operated selector switch on the cabinet front of each DC module for inverter
enable/disable is set to OFF.
•
Check that the DC disconnector 11-QM1 in each DC module is open
•
Check that all the disconnect switches in the string boxes are closed
•
Check that all AC circuit breakers 30-QMx located on the AC modules are open (their number varies
based on the product configuration).
•
Close the upstream master switch to power supply the inverter AC output.
Inverter power supply:
•
Carry out at least one of the operations below to apply power to the inverter (the display on each DC
module will come on):
o
Enable auxiliary power supply from UPS
o
Enable auxiliary power supply
o
If the
Self-consumption option
is installed, close the AC circuit breaker
•
When the displays are on, make sure that no alarm have tripped or warning has fired
•
If still open, close the AC circuit breaker. After a few seconds the GRID LED on the display comes on.
NOTE
The optional Interface Protection (IP) is sensitive to the phase sequence of the grid voltage. If
installed and the GRID LED does not light up on the display this may be due to incorrect phase
sequence. Check the LED indicators on the device. If necessary, invert the two phases on the
X1 terminal board.
•
Close the DC disconnect switch. If the PV field voltage is above the minimum threshold, the “PV OK”
LED comes on.
•
Do the following on the first DC module:
o
Turn the enable/disable key-operated selector switch to START
o
Press the button from the keypad. If the no-load voltage of the PV field exceeds the value set
in parameter P020*1.1 in the PV Field menu, the inverter will run and will start delivering power
to the grid.
•
Repeat the operations listed above for each DC module.
NOTE
Pressing of the START button is a condition stored in the system memory, hence, if the SUNWAY
TG TE power supply is cut off without an alarm tripping or without the STOP button being
pressed, the inverter will still have the RUN command active when the power supply comes back
on.